EasyManua.ls Logo

doble M4110 - Performing Tests on Different Transformer Types

doble M4110
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Leakage Reactance Test Procedures
3-4 72A-2243-01 Rev. B 9/04
September 17, 2004
NOTE These test connections represent common transformer winding vector
relationships. Always check your transformer nameplate drawing to be
sure the phase short-circuited corresponds to the phase energized! The
consequence of short-circuiting the wrong winding will be that the tester
will not be able to obtain the recommended current to run the test. For
example, for a Per-Phase Wye test, a transformer with the following
vector representation of its winding relationship would require the
different connections shown:
Figure 3.1 Example of Transformer Winding Vector Diagram Requiring
Modified Leakage Reactance Test Connections
Test Procedures for a Two-winding Three-Phase Unit
With the M4000 insulation analyzer, which uses single-phase excitation, the
leakage reactance of a three-phase unit can be measured using two methods:
the three-phase-equivalent test and the per-phase test.
Table 3.1 Example of Modified Connections for Leakage Reactance
Per-Phase Wye Test
Connections Shown In
Manual For Per-Phase Wye
Test
Connections Required by
Per-Phase Wye Test For
Wye-Delta Vector Diagram
Shown Below
Energize Short Energize Short
H1-H0 X1-X3 H1-H0 X2-X1
H2-H0 X2-X1 H2-H0 X3-X2
H3-H0 X3-X2 H3-H0 X1-X3