[CHAPTER 6 FUNCTION TABLE & DESCRIPTION]
6-3 |
DOOCHPUMP
Name Range
Factory
Setting
Para.
Link
Diff.
Pressure
Use
Change
on
Operation
Ref.
Page
Pr-52 CAN Comm. Speed 1~5 1 X O X
6-11
Pr-53 Alteration type 0~1 0
Pr-54
Lead pump
alternation time
0~24(hour) 12 O O O
Pr-55
Standby Pump wating
time
0~100[sec] 5 Ο Ο O
Pr-61
PID control Type
Setup
0~1 0 O O X
6-12
Pr-64
Output Ratio of
Starting AllPID
Increase
70~100[%] 100 O O O
Pr-70
High Pressure Alarm
Level
0~Sen1 Capacity
[bar]
16.0 Ο Χ O
Pr-71
Low Pressure Alarm
Level
0~10.0[bar] 0.5 Ο Χ O
Pr-72
High Pressure Alarm
Time
0~100[sec] 5 Ο Χ O
Pr-73
Low Pressure Alarm
Time
0~200[sec] 20 Ο Χ O
Pr-74
Low Level Trip Time
of Pressure Sensor
0~250[sec] 20 Ο Χ O
Pr-75
Low Level Trip
Pressure Level
0~1.0[bar] 0.3 Ο Χ O
Pr-76
Low Level Detection
Method Selection
0~1 0 X Χ X
6-13
6-14
Pr-77
Low Level Trip Time
of Low Level Sensor
0~250[sec] 2 Ο Χ O
Pr-80 Fault History - - X O X
Pr-81 Fault History 1 - - X O X
Pr-82 Fault History 2 - - X O X
Pr-83 Fault History 3 - - X O X
Pr-84 Fault History 4 - - X O X
Pr-85 Fault History 5 - - X -O X
Pr-86 Delete Fault History 0~1 0 X O O
Pr-87 Sensor percentage 0~200 100 X X O
6-15
Pr-90 Initialization Code 0~1 0 X O X
Pr-92 S/W Version - - X O X