[CHAPTER 6 FUNCTION TABLE & DESCRIPTION]
Setup Data Functional Description
Single Mode0(Factory Setting)
Related Functions
dr-02 Target Frequency Input Method
Pr-52 CAN Communication Speed
Pr-53 Lead Pump Alternation method
Pr-54 Lead Pump Alternation Time
Pr-55 Stand-by Pump Waiting Time
1~6
Multi-Drive
control
Comm. ID
No.
Pr-61 PID Type on Multi-Drive control
Pr-52 CAN Communication Speed
It sets up CAN communication speed. In case of long connection distance, it is better to reduce
the communication speed.
Setup Data Functional Description
40kbps1(Factory Setting)
50kbps 2
100kbps 3
200kbps 4
250kbps 5
Pr-54 Lead Pump Alternation Time
Alternative operation refers to an operation that when it reaches time specified by the user, the
drive with a lot of power consumed is to be stopped and the one with less power consumption is
to be started alternatively at the same time in order to prevent a specific drive(pump) being
operated constantly. If times is set, drives are forcedly shifted.
Setup Data Functional Description
Release of alternation 0
1~24(hour) Alternation time setup. (Factory Setting 12[hour])
Pr-53 Alternation method
It determines the order of Q-Driver’s run, stop, alternation on Multi-Drive operation mode.
* Setting is available for Ver 1.3x
* When Pr-50 can comm. mode is 0, alternation is set 0.
Setup Data Functional Description
In order if ID1(Factory Setting)
0 In order of low watt-hour
6-11 |