[CHAPTER 7 CAUSE OF FAULT AND REACTION]
7-6 |
DOOCHPUMP
Er-10 (Low Voltage Trip-tLv)
Cause
Occurred when the power supply voltage is low
Occurred when the connected load is larger than the power capacity
Reaction
Check the drive input voltage.
Check the power capacity.
It is possible to check the DC Link voltage on FND display part.
Er-11 (High Voltage Trip-tOv)
Cause
Occurred when the deceleration time (dr-23) is short comparing to the load inertia.
Occurred when the drive input voltage is too high.
Reaction
Increase the deceleration time (dr-23).
Check the driver power supply voltage.
It is possible to check the DC Link voltage on FND display part.
Related Function Function Name Ref. Page
6-18Falling Timedr-23
Er-12 (Motor Overload Operation Trip-tOL)
Cause
It generates an alarm and stops operation to protect the motor when the load is above the
overload trip level of the motor rated current (dr-31) and the motor operates for more than
overload trip time (dr-32). That is, if the rated current of the motor is 10[A], the overload trip
level is 120%, and the overload trip time is 5 seconds, the overload operation trip will be
generated when the pump operates above 12[A] of output current for more than 5 seconds.
Reaction
Check the rated current of the motor (on the nameplate) and the rated current setting (dr-12).
It is possible to check the DC Link voltage on FND display part.
Related Function Function Name Ref. Page
Motor Capacitydr-10
dr-12 Rated Current of Motor
6-16
6-18
6-19
dr-30 Motor Overload Trip Selection
dr-31 Motor Overload Trip Level
dr-32 Motor Overload Trip Time
*
*
*