ONRZ
C1 OPERATING DATA
Defrosts
7
Per Day
Run-Off
Time (min)
Electric Defrost Timed-Off Defrost Hot Gas Defrost
Fail-Safe
(min)
Termination
Temp (°F)
Fail-Safe
(min)
Termination
Temp (°F)
Fail-Safe
(min)
Termination
Temp (°F)
1 13 - 15 46 60 - - -
8
- - - 24 73
1 Tank heater and fan motors share the same circuit (seperate cycles). Be certain that the circuit wiring is properly sized to handle the higher current draw of the tank heater.
2 3-phase load is unbalanced.
3 Figure given is maximum line amperage per phase.
4 Low-power lights. High-power option available.
5 Values provided are for doors with no heat on the glass.
6 Average discharge air velocity at peak of defrost.
7 If a discharge air temperature sensor is used to terminate defrost cycle, termination temperature should be set to 55ºF.
8 NOTE: “- - -” indicates that the feature is not an option with this case model.
Guidelines & Control Settings
Defrost Controls
Application Door
BTUH/door
Evaporator
(°F)
Superheat
Set Point @ Bulb
(°F)
Discharge
Air
(°F)
Discharge
6
Air
Velocity
(FPM)Conventional Parallel
Frozen ELMD/Polar RE 1044 1014 -7 3 - 5 -3 400
Eliminaator/2; Polar LE/EF (multi-door) 988 960 -7 3 - 5 -3 400
Ice Cream ELMD/Polar RE 1091 1060 -15 3 - 5 -10 400
Eliminaator/2; Polar LE/EF (multi-door) 1027 998 -15 3 - 5 -10 400
Doors
Anthony Gemtron
ELMD Eliminaator
5
Eliminaator 2
5
Polar RE Polar LE Polar EF
120 Volts 120 Volts 120 Volts 120 Volts 120 Volts 120 Volts
Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts
2-door 2.1 256 1.7 209 1.2 145 2.1 254 1.4 166 1.2 140
3-door 3.2 378 2.6 309 1.8 213 3.2 378 2.1 246 1.7 207
4-door 4.2 502 3.4 403 2.3 276 4.2 501 2.7 325 2.3 273
5-door 5.2 625 4.2 506 2.9 346 5.3 632 3.4 412 2.9 347
6-door 6.2 743 5.1 607 3.5 416 6.2 747 4.0 483 3.4 405
Electrical Data
Anti-Condensate Heater Data
Doors
Fans
Per Case
High Efciency
Fans
Tank
1
Heater
Defrost Heaters
(1-Phase)
Defrost Heaters
2
(3-Phase)
120 Volts 120 Volts 208 Volts 240 Volts 208 Volts 240 Volts
Amps Watts Amps Watts Amps Watts Amps Watts Amps
3
Watts Amps
3
Watts
2-door 2 0.6 50 1.3 152 7.5 1552 8.6 2068 6.5 1552 7.5 2068
3-door 3 1.0 75 1.5 171 10.9 2274 12.6 3018 9.5 2274 10.9 3018
4-door 4 1.3 100 1.9 226 14.3 2984 16.6 3992 12.4 2984 14.4 3992
5-door 5 1.6 125 2.3 275 17.5 3640 20.2 4840 15.1 3640 17.4 4840
6-door 6 1.9 150 2.7 320 20.3 4224 23.4 5624 17.6 4224 20.3 5624
Lighting Data
Doors
LED Lighting
Optimax
Pro
4
GE
IMMERSION
Crossre
4
/Polaris
120 Volts 120 Volts 120 Volts
Amps Watts Amps Watts Amps Watts
2-door 0.3 39 0.3 32 0.3 30
3-door 0.5 58 0.4 48 0.4 45
4-door 0.6 77 0.5 64 0.5 60
5-door 0.8 96 0.7 80 0.6 75
6-door 1.0 115 0.8 96 0.8 90