TECHNICAL REFERENCE
ENGINEERED FOR STORES WITH AMBIENT
CONDITIONS NOT TO EXCEED 75° AND 55%
RELATIVE HUMIDITY. DUE TO ENGINEERING
IMPROVEMENTS SPECIFICATIONS MAY CHANGE
WITHOUT NOTICE. ALL MEASUREMENTS ARE
TAKEN PER ASHRAE-72-2005 SPECIFICATIONS.
HILLPHOENIX REFRIGERATED DISPLAY CASES
FOR SALE IN THE UNITED STATES MEET OR EXCEED
DEPARTMENT OF ENERGY 2017 REQUIREMENTS.
NUMBERS ARE BASED ON STANDARD CASE SIZES.
CONSULT ENGINEERING.
QC-30-R
Self-Service Open Multi-Deck In-Line Air Screen Merchandiser
4', 6', 8', 10' & 12' (Beverage/Dairy/Deli/Produce)
QC-30-R
Rev. Date Rev. # Rev. Title
10-14-20 2 ENDVIEW UPDATE
09-03-20 1 NEW STANDARDS
NOTES:
• "---" Indicates that the feature is not an option on this case model and/or the data is not yet available at this time.
• Listed BTUH indicates unlighted shelves. Add the following for lighted shelves:
- 4' Shelf LED: 36 BTUH
- 4' Canopy LED: 72 BTUH
- 3' Shelf LED: 27 BTUH
- 3' Hi-Output LED: 54 BTUH
• Listed discharge air velocity represents the average velocity at the peak of defrost.
* Time-off duration for defrost with no termination control.
ELECTRICAL DATA
Case
Length
Fans
Per
Case
High Efficiency
Fans
Anti-Condensate
Fans
Drain
Heaters
Optional Defrost
Heaters
120 Volts 120 Volts 120 Volts 208 Volts
Amps Watts Amps Watts Amps Watts Amps Watts
4' 2 0.60 72.0 --- --- --- --- --- ---
6' 4 1.20 144.0 --- --- --- --- --- ---
8' 4 1.20 144.0 --- --- --- --- --- ---
12' 6 1.80 216.0 --- --- --- --- --- ---
LIGHTING DATA
Case
Length
Lights
Per
Row
Light
Length
Clearvoyant 4 LED Lighting
(Per Light Row)
Standard Power
(Cornice or Shelf)
High Power
(Cornice)
120 Volts 120 Volts
Amps Watts Amps Watts
4' 1 4' 0.05 5.9 0.12 14.9
6' 2 3' 0.08 9.4 0.20 23.8
8' 2 4' 0.10 11.8 0.24 29.8
12' 3 4' 0.15 17.7 0.36 44.7
GUIDELINES AND CONTROL SETTINGS
BTUH/ft Superheat
Set Point @ Bulb
(°F)
Evaporator
(°F)
Discharge Air
(°F)
Discharge Air
Velocity
(FPM)
Conventional Parallel
1526 1407 10 24 28 170
DEFROST CONTROLS
Defrosts
Per Day
Run-Off
Time
(Min)
Electric Defrost Timed-Off Defrost Hot Gas Defrost
Fail-Safe
(Min)
Termination
Temp
(°F)
Fail Safe
(Min)
Termination
Temp
(°F)
Fail-Safe
(Min)
Termination
Temp
(°F)
6 0 --- --- 30/*15 45 --- ---