Rack Monitor 88XX
Document: Operation Manual
Date: January 2024
Version: A.0 subject to change
Page 41 of 43 Operations Manual
Condition
Possible Cause
Solution
The Rack Monitor doesn’t turn ON
The mains aren’t connected.
Connect the mains.
Check if the main wiring is
connected according to the
installation instruction.
Check if there is any power
available at the terminal of the
Rack Monitor 88XX.
The fuses are broken.
Replace the fuses for new ones.
Note: the fuses might have been
blown due to the high inrush current
of the power-supply. Always use
same rated fuses.
System goes directly into ‘NON
PERMISSIVE’
The dead man switch is not
connected.
Connect the cable according to
the installation manual.
Connect a bypass wire between
pin 1 & 2 according to the
installation manual.
System does not indicate correct
amount of compartments in
5-Wire mode
Bad connections in sensor
housing and/or plug/socket.
Check green and white wires
Clean pin 5 and 10 on plug and
socket
For all other possible inflictions/damages to the Rack Monitor 8800E/8801E, contact OPW Engineered Systems
Customer Service and ask for assistance to obtain a safe and right use.
Annex A Additional Electrical Drawings
Ask OPW for different connection diagrams e.g. dual socket or junction box