LIM (Line Interface Module)
9. Device: Select the LIM address identification number from the drop-down (select 1 through 4). Each
LIM module must have its own LIM address. Use the rotary switch on the LIM board to configure the
LIM address.
INFORMATION: Refer to the M00-20-8321-LIM LIM Procedure Guide for information on
configuration of the LIM device..
10. Channel: Select the LIM Channel from the drop-down (1 through 4) where the applicable STP is
connected
Pipeline
1. Line length: Enter the total length of the pipeline (from the STP to the last dispenser. Include the
length of all branches that are installed between the STP and dispensers)
2. Pipeline: A series of specific pipelines is included in this field. The user can select a pipeline and the
system will automatically populate the volume/length parameter in the next field.
NOTE: If your pipeline is not listed here, you can select the closest pipeline and manually
enter the volume/length parameter in the next field (it will override the automatically selected
volume/length).
M2051_r4 MagLink LX 4 and LX Plus Configuration Manual | Dover Fueling Solutions 86