process from the forecourt (the technician lifts the nozzle for 2 seconds and puts the nozzle back in
the cradle. The calibration will then start).
13. Calibration status: This is an information window that shows the current status of the process.
14. START button: This starts the calibration sequence (this can be immediately or through the nozzle
signal . Refer to “Start calibration immediately" in the previous step.).
15. STOP button: This will stop the calibaration sequence.
Click the SAVE button to save the current pipeline setup.
NOTE: If the DELETE button is selected, it will erase the PLLD configuration.
Leak Test
Automatic LLD leak test – click the Save button to save the settings
1. Enabled: When this button is “Enabled,” the system will run a leak test automatically that uses
specified frequencies.
M2051_r4 MagLink LX 4 and LX Plus Configuration Manual | Dover Fueling Solutions 88