Appendix How to Configure a Siemens LR120
Radar
Before you connect the Siemens LR120 Radar to a Maglink LX console, the SIEMENS mobile IQ app must
be used to configure the device.
l After you connect the Radar device to a power source (8-30 V DC), a Bluetooth PIN is required to
connect to the device.
l When a connection has been made, go to Se t up > De t ai l ed s e tu p > Co m m u ni c at i on >
Ad d r e s s , and change the address (the default is 246). This address will show as a Serial Number in
the Maglink LX.
IMPORTANT: Separate addresses must be set up for each site. Two or more Radar devices
cannot have the same address.
l After address configuration, the Radar device can be connected to the Maglink LX console.
l On We b U I > T a nk s s e t u p > S e tt i ng s S e r i al Nu m b e r, the Radar device address must be
entered. After "QUERY PROBE" the system should automatically adjust the probe type to "Radar
LR120."
(Continued on next page)
M2051_r4 MagLink LX 4 and LX Plus Configuration Manual | Dover Fueling Solutions 96