Introduction
The FSA-210 is a 2-wire photoelectric smoke detector with
optional: fixed temperature heat detector, internal piezoelectric
alarm, auxiliary form C relay, and/or remote LED output. Three
version are available: US version (UL), Canadian version (ULC)
and an International version (EU).
Operation
Approximately every 7 to 8 seconds the unit tests for a smoke or
heat alarm condition. During this sequence the unit also per-
forms self diagnostics, and checks for faults. During normal
operation the LED will flash every 50 seconds and the sounder
will not sound.
Smoke Alarm
The smoke detector has a nominal fixed alarm sensitivity (refer
to the Specifications on the last page) and it will go into alarm
when the signal level exceeds the 'alarm' threshold and send
the alarm signal to the control panel. During an alarm the LED
will flash 1/second and the sounder will sound the the evacua-
tion temporal pattern (UL, EU) or continuous beeps (ULC).
Remote Alarm - Interconnection
Multiple detectors (with sounders) can be connected using the
PRM-2W Polarity Reversal Module. When a fire alarm occurs,
the panel will signal the PRM-2W to reverse the polarity of the
2-wire loop. This will activate the sounders of all units con-
nected on the loop. Refer to the PRM-2W/4W Installation
Instructions for installation details.
Smoke - Drift Compensation
The detector automatically compensates for long-term environ-
mentally induced changes to maintain a constant smoke sensi-
tivity. When the drift compensation has reached its high or low
limit of adjustment, the detector will go into the trouble state.
Heat Alarm
The heat detector will go into alarm when the heat signal level
exceeds the heat alarm threshold (135ºF/57ºC); and send the
alarm signal to the control panel. During an alarm the LED will
flash 1/second and the sounder will sound the evacuation tem-
poral pattern (UL, EU) or continuous beeps (ULC).
Installer Instructions
1. Smoke Detector Placement
On smooth ceilings, detectors may be spaced 9.1M (30 feet)
apart as a guide. Other spacing may be required depending on
ceiling height, air movement, the presence of joists, uninsulated
ceilings, etc. Consult National Fire Alarm Code NFPA 72, Chap-
ter 11 CAN/ULC-S553-02 or other appropriate national stan-
dards for installation recommendations.
Do NOT locate smoke detectors at
the top of peaked or gabled ceilings;
the dead air space in these locations
may prevent the unit from detecting
smoke. Avoid areas with turbulent
air flow, (near doors, fans or win-
dows. Rapid air movement around
the detector may prevent smoke
from entering the unit. Do NOT
locate detectors in areas of high
humidity.
Do NOT locate detectors in areas where the temperature rises
above 38ºC (100ºF) or falls below 5ºC (41ºF).
FSA-210 Series Smoke Detector
Installation and Operating Instructions
Read this instruction sheet thoroughly before installation and use of the FSA-210 2-Wire Smoke Detector
P
A
I
N
T
Piezo Sounder
Alignment Marks
LED/Test Button
Place magnet here
DO
N
O
T
Alarm Indications
Condition LED Sounder Relay
Alarm
Current
Normal / Sensitivity
in Production
Range
Flash 1/50s OFF Deactivated No
Alarm Smoke/Heat Flash 1/1s
Temporal or
Steady
Activated Yes
Alarm Restore Flash 1/1s
Temporal or
Steady
Activated Yes
Remote Alarm Flash 1/50s
Temporal or
Steady
Deactivated No
Low Power Trouble OFF OFF Deactivated No
Other
Fault / Trouble
OFF
CHIRP 1/
50s
Deactivated No
Test Switch -
Failed
OFF
CHIRP 1/
50s
Deactivated No
Test Switch - Pass Flash 1/1s
Temporal or
Steady
Activated Yes
Question and Answer IconNeed help?

Do you have a question about the DSC FSA-210 and is the answer not in the manual?

DSC FSA-210 Specifications

General IconGeneral
BrandDSC
ModelFSA-210
CategorySmoke Alarm
LanguageEnglish

Summary

Installer Instructions

Smoke Detector Placement

Guidelines for positioning smoke detectors on ceilings, considering spacing and environmental factors.

Mount Smoke Detector Backplate

Instructions for mounting the detector backplate to an electrical box using provided screws.

Wiring

Guidance on preparing and connecting wires from the electrical box to the detector unit.

Mounting

Procedure for attaching the detector to its base plate and locking mechanism.

Test Unit

Steps for testing the smoke detector using a magnet or test button, including alarm indications.

Compensation Reset

Procedure to reset the detector's drift compensation after changes or trouble states.

Owner's Instructions

Fire Safety In The Home

Recommendations for household fire safety audits and developing a family escape plan.

Household Fire Safety Audit

Checklist for evaluating electrical appliances, flammable liquids, and hazardous materials.

Family Escape Planning

Guidance on creating and rehearsing a family escape plan, including escape routes and assembly points.

Testing Your Smoke Detector

Instructions for weekly testing of smoke detectors using a pushbutton or magnet.

Maintenance

Recommendations for cleaning the detector case and avoiding disassembly or painting.

Product Information and Compliance

Smoke Detector Family

Overview of the FSA-210 series smoke detectors and model variations with features.

Specifications

Technical details including dimensions, operating temperature, humidity, and sensitivity.

Limited Warranty

Details of the twelve-month warranty for defects in materials and workmanship.

FCC Compliance Statement

Information regarding compliance with FCC rules for digital devices and interference.