Introduces and lists common fault codes for the Dungs MPA-4112 Flame Management system.
Explains F04 fault occurs after 5 resets in 15 mins; can be reset by holding Enter.
Indicates a broken safety chain before heat enable, possibly due to pressure switch bounce or high temp limit.
Caused by bouncing pressure switch or external voltage; suggests testing by jumpering terminals 9 & 10.
Safety chain broken with heat enable present, often due to airflow pressure switch bounce.
Indicates combustion air confirmation issue, likely pressure switch failure before heat enable.
Signals no flame detected during ignition trial; suggests resetting if safeties are in place.
Flame extinguishes during operation due to air in line, low fire, or poor flame rod signal.
Flame failure post-ignition stabilization, possibly due to air in line or low fire setting.
POC error on valve #2, often due to loose set screw affecting switch indication.
Explains how to view the last 10 error codes using MPA display buttons.
Details how to check flame rod signal strength and clean/replace it for optimal performance.
Introduces and lists common fault codes for the Dungs MPA-4112 Flame Management system.
Explains F04 fault occurs after 5 resets in 15 mins; can be reset by holding Enter.
Indicates a broken safety chain before heat enable, possibly due to pressure switch bounce or high temp limit.
Caused by bouncing pressure switch or external voltage; suggests testing by jumpering terminals 9 & 10.
Safety chain broken with heat enable present, often due to airflow pressure switch bounce.
Indicates combustion air confirmation issue, likely pressure switch failure before heat enable.
Signals no flame detected during ignition trial; suggests resetting if safeties are in place.
Flame extinguishes during operation due to air in line, low fire, or poor flame rod signal.
Flame failure post-ignition stabilization, possibly due to air in line or low fire setting.
POC error on valve #2, often due to loose set screw affecting switch indication.
Explains how to view the last 10 error codes using MPA display buttons.
Details how to check flame rod signal strength and clean/replace it for optimal performance.