Detection of Toxic, explosive gases & O
2
3 Stages of Alarm - 1
st
& 2
nd
level and Main Alarm
Digital display - Colour change feature in Alarm
Microprocessor control
Wall or panel fascia mounted
For up to 4 Sensor
4 - 20mA signal input from each sensor
Measuring range 0 - 20% LEL / 0 -
300ppm
NEW - Oxygen Depletion or excess monitoring
IP44 protective rating
CE Certified and approved to EN50194 for
explosive
gases and EN50291 for toxic gases
2 year Warranty - extendable to 3 years by registering
this product on-line www.duomo.co.uk
Features
The BX444-M is a wall or panel mounted microprocessor
based gas detector control unit. It can be configured to
meet customer requirements. The following parameters
can be changed using on board DIP switches:
Number of sensors from 1 to 4
Type
of gas to be sensed (explosive or toxic)
Display type, either LEL or ppm
Intrinsic safety option (on or off)
Main alarm relay action (latching or auto-reset)
Oxygen Depletion or Excess monitoring
Application
Duomo is recognised within the gas industry for
providing a comprehensive range of low cost, high
reliability gas detection for many applications. Duomo
Gas detectors are installed in locations such as boiler
rooms, kitchens, car parks, aircraft hangers,
factories and shopping centres. The BX444-M is the
command centre for the complete range of Duomo
gas sensors. All Duomo products are manufactured
to meet relevant European Normatives and proposals
for explosive and toxic gases. EN50194 EN50291
EN50270 EN 61010-1 and designed to be installed to
EN60079-29-2.
Operation
When any connected sensor detects the presence of
the targetgasa4-20mA signal is sent to the
detector, proportional to the level of gas. The
BX444-M then operates a pre-alarm relay - used for
remote sirens or visual indicators. If the level of gas
continues to rise then the second pre-alarm is
actuated. In the case of explosive gases, when the
level of gas reaches 20% LEL, the main alarm relay is
activated to break the electrical supply to the gas
safety shut-off valve (SSOV). The BX444-M also has a
separate volt-free sensor fault relay that actuates if the
correct return signal is not sensed by the detector. The
BX444-M can be configured to detect explosive or toxic
gases. The backlit colour display scrolls through each
sensor and reports their individual status.
CAUTION!
Carefully read the following instruc tions prior to
installation of this device. Always keep this pamphlet for
future reference. Ensure that the gas detection system is
wired correctly and is only used for the purpose for
which it is intended.
BX444-Mc Gas Detector
i
w: www.duomo.co.uk - e: sales@duomo.co.uk - t: 01905 797989 - f: 01905 774296 |
© Duomo (UK) Ltd. 2016
Installation and User Guide Rev.01.
The
New BX444Mc has a TEST timer function for use by
service and commissioning engineers only. The
controller has a built in sensor test delay that permits the
main alarm relay - in a typical installation operates the
gas valve - to remain on during the alarm phase of a gas
test. This is a great feature in situations where shutting
down the gas supply to boiler plant and other
appliances is not desirable. For more information call the
Duomo technical department on 01905 797989.

Questions and Answers

  • B
    Beth JonesAug 1, 2025
    What to do if Duomo Gas Detectors are subject to repeated alarms?
    • B
      bishopdanielAug 1, 2025
      If your Duomo Gas Detectors are experiencing repeated alarms, make sure there isn't an occasional gas leak. This could be due to a valve or joint that leaks when under pressure.
  • R
    Robin VillanuevaAug 5, 2025
    What to do if Duomo BX444-Mc are in main alarm but the main gas valve isn't closing?
    • S
      Samantha MoralesAug 5, 2025
      If the Duomo Gas Detectors are in a main alarm condition but the main gas valve is not closing, verify that the connections are correct and that power is supplied to the valve, ensuring it's not stuck open. You can check the alarm relays' function by pressing the TEST button. Also, confirm that the main alarm action is configured for a latching alarm (Switch 2 on 5th DIP switch).
  • J
    Joel SanchezAug 9, 2025
    Why is sensor fault continuing to alarm in Duomo BX444-Mc?
    • D
      Deborah DelgadoAug 9, 2025
      If a sensor fault continues to alarm in Duomo Gas Detectors, it could be due to the red Overload LED being lit. Check the sensor wiring. If the red Overload LED is lit, it indicates a short circuit or overload on the sensor or the connecting cable.
  • A
    andrewbarnesAug 14, 2025
    How to fix Duomo BX444-Mc when one or all of the sensor fault lights are illuminated?
    • S
      Sarah McleanAug 14, 2025
      If one or all of the sensor fault lights are illuminated on your Duomo Gas Detectors, check that the plug is inserted correctly and that the sensor wiring is correctly terminated at both the sensor and detector. Also, ensure that 12V DC is present at the sensor, with the green light on the sensor illuminated. Pressing the TEST button allows you to check the efficiency of the device and verify if the sensors have been connected correctly.
  • T
    timothy21Aug 18, 2025
    How to troubleshoot no supply to the solenoid valve in Duomo BX444-Mc Gas Detectors?
    • T
      Travis BradshawAug 18, 2025
      If there's no supply to the solenoid valve in your Duomo Gas Detectors, remember that the Main Alarm relay is a volt-free contact. Therefore, connect the live supply to the common of the main alarm relay contacts terminal 10. A supply will then come from terminal 12 to the solenoid valve.
  • J
    Jennifer MitchellAug 22, 2025
    How to fix Duomo Gas Detectors when no lights are illuminated?
    • A
      Alicia GonzalesAug 23, 2025
      If no lights are illuminated on the fascia of your Duomo Gas Detectors, check that the electrical supply is reaching the device and that the plug in terminal rail is pushed into place.
  • M
    Mark BowmanAug 27, 2025
    What to do if sensor is connected, but no LED is lit on the front fascia of Duomo BX444-Mc?
    • M
      Michael JonesAug 27, 2025
      If the sensor is connected, but no LED is lit on the front fascia of your Duomo Gas Detectors, check that the DIP switch is set to the ON position.

Summary

Application

Features

Features Overview

The BX444-M is a wall or panel mounted microprocessor based gas detector control unit.

TEST Timer Function

The controller has a built in sensor test delay that permits the main alarm relay to remain on during a gas test.

Safety Caution

Carefully read the following instructions prior to installation of this device. Always keep this pamphlet for future reference.

Operation

Technical Specification

Fascia & PCB Layout

Display Description

Wiring and Installation

Electrical Installation

The BX444-Mc is a safety device designed to give audible alarms and automatically provide latched electrical isolation of associated gas safety shut off valves.

Installing a Sensor

The sensors must be mounted as shown below with the sintered head pointing vertically down.

Important Notes

Always check the wiring before powering up the system. Do not test this sensor with anything other than Duomo test gas.

Configuring The BX444-Mc

Zone ON;OFF Configuration

Zone ON or OFF - The BX444-Mc will not look for a sensor on a given zone if the switch is moved to the OFF position.

Gas Type Configuration

Type of gas to be sensed. These are labelled as GAS or CO. Symbols refer to EN standard symbols.

Positive Safety Configuration

Positive safety determines the condition of the main alarm relay and hence the operation of the gas valve.

Main Alarm Relay Configuration

Main Alarm relay actuation method. Configurable for latching or temporary alarm operation.

BX444-Mc Operation Details

Memory Mode Configuration

Determines whether the audible alarm remains operational after levels have dropped. In memory mode, the alarm remains and will need to be manually reset.

Oxygen Level Monitoring

Configured to indicate oxygen levels. The function is determined by setting either excess oxygen or oxygen depletion on the sensor itself.

Power-up Sequence and Test

Details the power-up sequence, LED checks, sensor warm-up period, and manual TEST button function.

In Case of Alarm

Troubleshooting

Commissioning

Maintenance

Duomo BX444-Mc Specifications

General IconGeneral
Detection GasesCH4, CO, H2S, O2
Detection Range (CH4)0-100% LEL
Detection Range (H2S)0-100 ppm
Operating Temperature-20°C to +50°C
Power SupplyRechargeable Li-ion battery
Sensor TypeElectrochemical
Alarm SetpointsAdjustable
DisplayLCD
AlarmsAudible, Visual, Vibration
Protection RatingATEX, IECEx