17
ALrE
 (Alarm Reset) SUB MENU
ONOF
- Automatic reset
HOLD
- Manual reset. An alarm is reset by the RESET key on the front 
panel, or an external reset switch.
AL.H
 (Low Alarm Inhibit) SUB MENU
ON
- Alarm inhibit is on
OFF
- Alarm inhibit is off
If 
AL.H
is selected ON, a low alarm condition is suspended upon power 
up until the process value passes through the alarm set point once.
ALDL
 (Alarm Delay) SUB MENU
Sets the amount of time an alarm condition must be continuously met before 
the alarm condition is recognized. The alarm delay is adjustable from 0-3600 
seconds.
d.S
 (Display) MAIN MENU
PEAK
- Peak value
rESO
- Resolution
VALy
- Valley value
Pd.S
- Process display
ZERO
- Zero
DAMP
- Dampening level
PEAK
 (Peak) SUB MENU
The Peak feature stores the highest pressure reading the instrument has 
measured since the last reset or power up. At power up 
PEAK
is reset 
to the present pressure reading. To manually reset the 
PEAK
value, 
press the RESET key while in the 
PEAK
SUB MENU.
VALy
 (Valley) SUB MENU
The valley feature stores the lowest pressure reading the instrument has 
measured since the last reset or power up. At power up 
VALy
is reset to 
the present pressure reading. To manually reset the 
VALy
value, press the 
RESET key while in the 
VALy
SUB MENU.