uoUt (Voltage Output Range) SUB MENU
The voltage output range setting allows the voltage output limits to be congured to 1
of 4 common ranges. Available options include: 0-10 V, 0-5 V, 1-5 V, and 2-10 V. The
factory setting is 0-10 V.
SP (Set Point) MAIN MENU
The SP MENU allows the individual set points to be enabled or disabled. The SUB
MENUS are:
SP1 - Set Point 1 Enable
SP2 - Set Point 2 Enable
SP1 (Set Point 1 Enable) SUB MENU
Enable/disable set point 1. When enabled (ON), the set point 1 trigger and reset SUB
MENUS will appear in the SPAL menu. The factory setting is ON.
SP2 (Set Point 2 Enable) SUB MENU
Enable/disable set point 2. When enabled (ON), the set point 2 trigger and reset SUB
MENUS will appear in the SPAL menu. The factory setting is ON.
AL (Alarm) MAIN MENU
The AL MENU allows the features of the alarm to be congured. The SUB MENUS are:
ALHi - Alarm High Limit Enable
ALLo - Alarm Low Limit Enable
ALrE - Alarm Reset Type
ALiH - Alarm Inhibit Enable
ALDL - Alarm Delay Time
ALHi (Alarm High Limit Enable) SUB MENU
Enable/disable the alarm high limit. When enabled (ON), the alarm high limit (ALHI)
SUB MENU will appear in the SPAL menu. The factory setting is ON.
ALLo (Alarm Low Limit Enable) SUB MENU
Enable/disable the alarm low limit. When enabled (ON), the alarm low limit (ALLO)
SUB MENU will appear in the SPAL menu. The factory setting is ON.
ALrE (Alarm Reset Type) SUB MENU
AUTO - Automatic reset (factory setting)
HOLD - Manual reset. An alarm is reset by the RESET key on the front panel.
ALiH (Low Alarm Inhibit) SUB MENU
ON - Alarm inhibit is on
OFF - Alarm inhibit is off (factory setting)
If ALiH is selected ON, a low alarm condition is suspended upon power up until the
process value passes through the alarm set point once.
ALDL (Alarm Delay) SUB MENU
Sets the amount of time an alarm condition must be continuously met before the alarm
condition is recognized. The alarm delay is adjustable from 0-3600 seconds. The
factory setting is 0.
rLy (Relay) MAIN MENU
The rLy menu includes options to congure which source will trigger a relay and what
happens when a relay is triggered. The SUB MENUS are:
rLy1 - Relay 1 Source
rLy2 - Relay 2 Source
r1At - Relay 1 Action
r2At - Relay 2 Action
rLy1, rLy2 (Relay 1 Source, Relay 2 Source) SUB MENUS
OFF - Relay not used
SP1 - Set Point 1
SP2 - Set Point 2
AL - Either Alarm
ALHI - High Alarm
ALLO - Low Alarm
EXT - External Input
The selected source determines when the relay is active. If the source is active, the
relay will be active.
r1At, r2At (Relay 1 Action, Relay 2 Action) SUB MENUS
DIR - Direct Acting/CLSE - Close on Active
REV - Reverse Acting/OPEN - Open on Active
The selected action determines what happens when the relay is active. If the selected
source is an alarm, then the options are CLSE and OPEN.
inP (Input) MAIN MENU
The inP MENU allows the features of the external input to be congured. The SUB
MENUs are:
inP - External Input Enable
tyPE - External Input Type
DLY - External Input Delay
inP (External Input Enable) SUB MENU
ON - External input enabled (factory setting)
OFF - External input disabled
tyPE (External Input Type) SUB MENU
NO - Normally Open (factory setting)
NC - Normally Closed
DLY (External Input Delay) SUB MENU
Sets the amount of time the external input must be continuously active before it is
considered active. The delay is adjustable from 0-3600. The factory setting is 0.
diS (Display) MAIN MENU
PEAK - Peak value
VALY - Valley value
PdiS - Process display
DAMP - Damping Time
PEAK (Peak) SUB MENU
The Peak feature stores the highest process reading the instrument has measured
since the last reset or power up. At power up PEAK is reset to the present pressure
reading. To manually reset the PEAK value, press the RESET key while in the PEAK
SUB MENU.
VALY (Valley) SUB MENU
The valley feature stores the lowest process reading the instrument has measured
since the last reset or power up. At power up VALY is reset to the present pressure
reading. To manually reset the VALY value, press the RESET key while in the VALY
SUB MENU.
PdiS (Process Display) SUB MENU
STD - Display reads pressure, velocity, or ow values
PCT - Display reads % of full-scale value
When the display is reading percent, PCT is displayed in the upper right of the display.
DAMP (Damping) SUB MENU
The damping time can be adjusted from 0 to 30 seconds.
Damping stabilizes the display and outputs from instabilities due to circumstances
such as vibration and excessive pressure uctuations. Adjust the damping value until
the display reads a stable value for the application.