Operation
4-16 Algas-SDI Operations & Maintenance Manual P/N 52632
Figure 7 – Control System
Control System.wmf
Control Board
BROWN-OUT FEATURE
The vaporizer is equipped with a Brown-Out feature. The Brown-Out feature will
return the vaporizer to normal operation if there is a power disturbance that is
less than 5 seconds. Do not get the Brown-Out feature confused with the Auto
Restart Option. The Brown-Out feature will only maintain vaporizer operation for
power disturbances less than 5 seconds. The Auto Restart Option will restart the
vaporizer if there is a loss of power for more than 5 seconds. If the vaporizer
should shut down on a safety during the above procedure, open the control box
and read the Operation / Fault code on the annunciator in the upper left corner of
the control board. The annunciator should display a failure code for reference in
troubleshooting. Follow the troubleshooting procedures in this manual to
determine the cause of the problem.
NOTE: Vaporizer controls prior to 53050-X series control board do not have a
brown-out feature.