EasyManua.ls Logo

ECOFOREST ecogeo basic - 3.8. Parameter Adjustment; 3.9. ON;OFF Menu

ECOFOREST ecogeo basic
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installer manual ecoGEO
45
EN
Figure 1.14.Bleeding the DHW production circuit in ecoGEO Compact models.
4.2. Filling the brine circuit
The brine system temperature can fall below 0°C, so a mixture of water/antifreeze must be used. It is recommended to use propylene
glycol as an antifreeze additive or ethylene glycol with a corrosion inhibitor. Please check local regulations before using any type of
antifreeze mixture.
When preparing the mixture, be careful to calculate the volume of antifreeze necessary to reach the desired degree of antifreeze
protection. It is recommended to use a mixture with a freezing point at least 10ºC below the nominal minimum temperature.
Brine circuit filling should be done with the filling unit installed in the return pipe and an external circulation pump, taking the
following steps.
1. Prepare the appropriate proportions of antifreeze mixture in external tank A.
2. Connect the external recirculation pump outlet to valve D.
3. Connect a transparent hose from valve E to antifreeze mixture tank A.
4. Close valve C and open filling valves D and E.
5. Start the external recirculation pump and keep it running until the return is completely free of air and the antifreeze mixture
is mixed perfectly.
6. Open valve C and keep the external pump connected to remove the air between valves D and E.
7. Close valve E and pressurise the circuit to target pressure. Make sure that the pressure does not exceed 3 bar (pressure gauge)
under any circumstance.
8. Close valve D.
After completing the brine circuit filling process, it is recommended to check the concentration of antifreeze mixture again using a
refractometer.
Manual trap

Other manuals for ECOFOREST ecogeo basic

Related product manuals