Do you have a question about the Ecojay SMartZone-4X and is the answer not in the manual?
| Zones Supported | 4 |
|---|---|
| Power Source | 24VAC |
| Number of Channels | 4 |
| Output Current | 1A per zone |
| Protection | Overload, Short Circuit |
| Operating Temperature | -10°C to 50°C |
Use STAT TYPE button to select Zone 4 for Fresh Air configuration.
Set the number of minutes per hour for fresh air run time in 5-minute increments.
Store fresh air settings by pressing STAT TYPE or waiting 5 seconds.
System automatically energizes fan and opens damper for configurable fresh air run time during equipment calls.
Connect switch/sensor to Zone 4 thermostat terminals to activate advanced fresh air features.
For basic fresh air, do not connect the advanced feature terminals.
Fresh air thermostat enables economizer by using outside air temperature to utilize outside air instead of compressor.
Y terminal on Zone 4 energized by outdoor sensor activates economizer mode during cooling calls.
Economizer mode opens FA damper, energizes fan, and prevents compressor use until temperature limits are met.
Wiring diagram for the Fresh Air Thermostat (AFET) and its connection to the Outdoor Air Sensor (OAS).
Use UP/DOWN buttons to set the outdoor temperature setpoint for economizer mode activation.
Press "Free Cool" button to toggle economizer control between OFF and AUTO based on outdoor temperature.
Press "Vent" button to manually turn fresh air ON/OFF, creating a demand call to the controller.