© 2010 UTC Fire & Security. All rights reserved. 1 / 8 P/N 3100008 • REV 4 • ISS 09AUG10
5531M and 5531MHV Adaptatone Installation
Sheet
Description
Edwards Adaptatone Millennium is intended for industrial
applications where high audible output and microcomputer
reliability are required. The Adapatatone Millennium series are
UL and cUL Listed as Audible Signal Appliances for use in the
hazardous locations listed in Table 1.
The Adaptatone operates from local power. It accommodates
up to four normally-open contacts on its inputs. The tone that
sounds in response to an active input is determined by setting
miniature programming switches inside the unit. Table 6 has
switch settings for setting tones.
Four tones may be programmed into the unit at any time.
These tones operate on a pyramid-type priority system. The
tone programmed on SW1 overrides the tones programmed on
SW2, SW3, and SW4. The tone on SW2 overrides the tones
programmed on SW3 and SW4. Likewise, the tone on SW3
overrides the tone programmed on SW4. The tone
programmed on SW4 has the lowest priority and cannot
override any other programmed tone.
Speaker direction and the output level are easily adjustable.
Recording a Voice Message (5531MV
Series)
WARNING: High voltage is present when product is
energized.
1. Put switches A and B on the programming dipswitch in the
proper position for the message to be recorded (Figure 6).
For programming a message longer than five seconds,
use Message Location 1.
Message
Location
Start Switch A
Settings
Switch B
Settings
1 0 Sec CLOSED CLOSED
2 5 Sec OPEN CLOSED
3 10 Sec CLOSED OPEN
4 15 Sec OPEN OPEN
2. Put switch PGM on the programming dipswitch in the
“CLOSED” position for programming mode (Figure 6).
3. Press and hold the record button while speaking clearly
into the microphone to record your message. Release the
button when recording is complete.
4. To test the message, press and hold PLAY while in
programming mode.
NOTE: This will play only the current location.
WARNING: High volume may cause harm to personnel in
close proximity.
5. Adjust the volume as necessary. Set the main volume
using the potentiometer on the main board (Figure 5 and
Figure 6) and then set the voice volume using the
potentiometer on the voice module board (Figure 6).
Installation
The Adaptatone may be mounted to any flat surface or may be
used as a freestanding unit mounted to a rigid pipe. The
Adaptatone must be installed in accordance with the latest
edition of the National Electrical Code or other regulations
applicable to the country and locality of installation and by a
trained and qualified electrician.
For catalog numbers ending in "AQ", 24 VAC power must be
transformer isolated from mains or line power.
Question and Answer IconNeed help?

Do you have a question about the Edwards Signaling 5531M and is the answer not in the manual?

Summary

Recording Voice Messages

Voice Message Recording Process

Outlines steps for programming dipswitch settings, recording a message, and testing it.

Volume Adjustment for Voice Messages

Details how to adjust main and voice module volume levels after recording.

Adaptatone Installation Guide

Mounting and Power Requirements

Describes mounting options and power isolation requirements for specific models.

Wiring and Tone Selection

Covers wiring instructions, connecting inputs, and selecting desired tones via programming switches.

Wiring the Adaptatone

Wire Routing and Separation

Details wire installation through knockout holes and using tie-wraps to separate leads.

Input Board Connections and Methods

Guides connections to the input board, including earth-ground, wiring methods, and power sources.

Maintenance and Testing Procedures

Product Specifications

Edwards Signaling 5531M Specifications

General IconGeneral
TypeSpeaker
Model5531M
Mounting TypeWall or Ceiling
Impedance8 Ohms
ColorRed
Sound Output82 dBA at 10 ft (3 m)
Operating Temperature32 to 120 °F (0 to 49 °C)
Humidity95% RH
Operating Voltage25V/70V
Voltage25V/70V