Table 6 continued
Parameters
Values
   
DC
250 V
АС
400 V
АС
690 V
DC
250 V
АС
400 V
АС
690 V
АС
400 V
АС
690 V
АС
400 V
АС
690 V
Rated peak
short-circuit
current Icm, kA
2,1xIcu 2,2xIcu
Rated insulation
voltage Ui, V
800
Utilization category
according to
IEC 60947-2:2016
A
Type of trip unit electromagnetic
Set point
of electromagnetic
trip unit
10xIn
Number of poles
(standard)
3P
Power
consumption, W
25 70 85 160
Protection degree IP30
Operating
temperature, °C
from – 25 to + 40
Weight, kg 1,25 2 5,75 24,6
Min. service life,
years
10