EasyManua.ls Logo

elco ELK 38 - User Manual

elco ELK 38
14 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
ELCO S.r.l. - ELK 38 - OPERATING INSTRUCTIONS - Vr. 02 - ISTR 06261 - PAG. 1
MICROPROCESSOR-BASED
DIGITAL
ELECTRONIC CONTROLLER
OPERATING INSTRUCTIONS
Vr. 02 (ENG) - cod.: ISTR 06261
EL.CO. S.r.l.
VIA MARCONI, 49
36030 PIEVEBELVICINO (VI) ITALY
TEL.: +39 0445 661722
FAX: +39 0445 661792
internet : http:\\www.elco-italy.com
e-mail: info@elco-italy.com
FOREWORD:
This manual contains the information necessary for the product to
be installed correctly and also instructions for its maintenance and
use; we therefore recommend that the utmost attention is paid to the
following instructions.
Though this manual has been issued with the greatest care, ELCO
S.r.l. will not take any responsibility deriving from its use.
The same applies to each person or Company involved in the
issuing of this manual.
This document is the exclusive property of ELCO S.r.l. which
forbids any reproduction and divulgation , even in part, of the
document, unless expressly authorized.
ELCO S.r.l. reserves the right to make any formal or functional
changes at any moment and without any notice.
INDEX
1 INSTRUMENT DESCRIPTION
1.1 GENERAL DESCRIPTION
1.2 FRONT PANEL DESCRIPTION
2 PROGRAMMING
2.1 FAST PROGRAMMING OF SET POINT
2.2
SELECTION OF CONTROL STATE AND PARAMETER
PROGRAMMING
2.3 PARAMETER PROGRAMMING LEVELS
2.4 CONTROL STATES
2.5 ACTIVE SET POINT SELECTION
3 INFORMATION ON INSTALLATION AND USE
3.1 PERMITTED USE
3.2 MECHANICAL MOUNTING
3.3 ELECTRICAL CONNECTIONS
3.4 ELECTRICAL WIRING DIAGRAM
4 FUNCTIONS
4.1 MEASURING AND VISUALIZATION
4.2 OUTPUTS CONFIGURATION
4.3 ON/OFF CONTROL
4.4 NEUTRAL ZONE ON/OFF CONTROL
4.5 SINGLE ACTION PID CONTROL
4.6 DOUBLE ACTION PID CONTROL
4.7 AUTO-TUNING AND SELF-TUNING FUNCTIONS
4.8
REACHING OF SET POINT AT CONTROLLED SPEED
AND AUTOMATIC COMMUTATION BETWEEN TWO
SET POINTS
4.9 SOFT-START FUNCTION
4.10 ALARM FUNCTIONS
4.10.1
ALARM OUTPUT CONFIGURATION
4.10.2
ALARM HYSTERESIS
4.11 LOOP BREAK ALARM FUNCTION
4.12 FUNCTION OF KEY “U”
4.13 PARAMETERS CONFIGURATION BY KEY01
5 PROGRAMMABLE PARAMETERS
5.1 PARAMETERS TABLE
5.2 PARAMETERS DESCRIPTION
6 PROBLEMS , MAINTENANCE AND GUARANTEE
6.1 ERROR SIGNALLING
6.2 CLEANING
6.3 GUARANTEE AND REPAIRS
7 TECHNICAL DATA
7.1 ELECTRICAL DATA
7.2 MECHANICAL DATA
7.3 MECHANICAL DIMENSIONS, PANEL CUT-
OUT AND
MOUNTING
7.4 FUNCTIONAL DATA
7.5 MEASUREMENT RANGE TABLE
7.6 INSTRUMENT ORDERING CODE
1 - INSTRUMENT DESCRIPTION
1.1 - GENERAL DESCRIPTION
ELK 38 is a “single loop digital microprocessor-based controller,
with ON/OFF, Neutral Zone ON/OFF, PID single action, PID dual
action (direct and reverse) control and with AUTO-TUNING FAST
function, SELF-TUNING function and automatic calculation of the
FUZZY OVERSHOOT CONTROL parameter for PID control.
The PID control has a particular algorithm with TWO DEGREES OF
FREEDOM that optimises the instrument’s features independently in
the event of process disturbance and Set Point variations.
The process value is visualized on 4 red displays, while the output
status is indicated by 2 LED displays.
The instrument is equipped with a 3 LED programmable shift
indexes .
The instrument provides for the storage of 4 Set Points and can
have up to 2 outputs: relay type or can drive solid state relays type
(SSR).
Depending on the model required the input accept:
C: Thermocouples temperature probes (J,K,S and ELCO IRS
Infrared sensors), mV signals (0..50/60 mV, 12..60 mV),
Thermoresistances PT100.
ELK 38
Question and Answer IconNeed help?

Do you have a question about the elco ELK 38 and is the answer not in the manual?

Overview

The ELK 38 is a single-loop, digital microprocessor-based electronic controller designed for various control applications. It offers ON/OFF, Neutral Zone ON/OFF, single-action PID, and dual-action PID (direct and reverse) control, incorporating AUTO-TUNING FAST and SELF-TUNING functions, along with automatic calculation of the FUZZY OVERSHOOT CONTROL parameter for PID control. The PID control algorithm features two degrees of freedom, optimizing the instrument's performance independently of process disturbances and Set Point variations.

Function Description:

The ELK 38 provides comprehensive control functionalities. It measures and visualizes process values on a 4-digit red display, with output status indicated by two LED displays. Three programmable shift index LEDs offer additional visual feedback. The instrument can store up to four Set Points and supports up to two outputs, which can be relay type or solid-state relay (SSR) drivers. Input options vary by model and include thermocouples (J, K, S, and ELCO IRS Infrared sensors), mV signals (0-50/60 mV, 12-60 mV), and Thermoresistances PT100. Other available functions include Loop-Break Alarm, controlled-speed Set Point reaching, ramp and dwell functions, Soft-Start, compressor protection for neutral zone control, and multi-level parameter protection.

The controller operates in three main states: automatic control (rEG), control off (OFF), and manual control (OPLO). It can transition between these states via the keyboard or automatically. In automatic control, the instrument resumes its last state upon power-up. Manual control allows programming of the output power percentage. The OFF state deactivates control and outputs, while alarm outputs remain active.

The AUTO-TUNING function enables fast calculation of PID parameters, which are then stored in memory. The SELF-TUNING function continuously monitors and calculates parameters during control. Both functions determine Proportional Band (Pb), Cycle time of output 1rEG (tcr1), Integral Time (Int), Derivative Time (dEr), and Fuzzy Overshoot Control (FuOC). For dual-action PID, Cycle time of output 2rEG (tcr2) and Power ratio 2rEG/1rEG (Prat) are also calculated.

The Soft-Start function, available for PID control, limits control power during instrument start-up for a programmable period. This is useful for protecting actuators from excessive power when the application is not at its normal rating. The ramp and dwell functions allow the Set Point to be reached at a controlled speed over a predetermined time, and enable automatic switching between two Set Points (SP1 and SP2) after a set duration, creating a simple thermal cycle.

Alarm functions include Absolute Low (LoAb), Absolute High (HiAb), Absolute Band (LHAb), Deviation Low (LodE), Deviation High (HidE), and Deviation Band (LHdE) alarms. Alarms can be configured with or without delay, as latched or non-latched, and with or without acknowledgment. Alarm hysteresis (HAL1) works asymmetrically, defining activation and deactivation thresholds. The Loop Break Alarm (LbA) activates if the control loop is interrupted due to probe issues or load interruption, providing a power output as programmed in "OPE" and displaying an "LbA" message.

Important Technical Specifications:

  • Power Supply: 12 VAC/VDC, 24 VAC/VDC, 115 VAC, 230 VAC, 100-240 VAC +/- 10%.
  • Frequency: 50/60 Hz.
  • Power Consumption: ~4 VA.
  • Input/s: 1 input for temperature probes (tc J,K,S; ELCO IRS J,K; RTD Pt 100 IEC; PTC KTY 81-121; NTC 103AT-2) or mV signals (0-50 mV, 0-60 mV, 12-60 mV) or normalized signals (0/4-20 mA, 0-1 V, 0-1.5 V, 0-2 V, 0-10 V).
  • Normalized Signals Input Impedance: 0/4-20 mA: 51 Ω; mV and V: 1 MΩ.
  • Output/s: Up to 2 outputs. Relay SPDT (8 A-AC1, 3 A-AC3 / 250 VAC) or tension to drive SSR (8mA/8VDC).
  • Auxiliary Supply Output: 12 VDC / 20 mA Max.
  • Electrical Life for Relay Outputs: 100,000 operations.
  • Installation Category: II.
  • Measurement Category: I.
  • Protection Class against Electric Shock: Class II for Front panel.
  • Insulation: Reinforced insulation between low voltage part (power supply 115/230 V and relay outputs) and front panel; reinforced insulation between low voltage section (supply 115/230 V and relay outputs) and extra low voltage section (input, SSR outputs); reinforced between power supply and relay. No insulation between supply 12 V and input, nor between input and SSR outputs.
  • Housing: Self-extinguishing plastic, UL 94 V0.
  • Dimensions: 33 x 75 mm, depth 64 mm.
  • Weight: ~180 g.
  • Mounting: Flush in panel in 29 x 71 mm hole.
  • Connections: 2.5 mm² screw terminals block.
  • Degree of Front Panel Protection: IP 65 mounted in panel with gasket.
  • Pollution Situation: 2.
  • Operating Temperature: 0 ... 50 ℃.
  • Operating Humidity: 30 ... 95 RH% without condensation.
  • Storage Temperature: -10 ... +60 ℃.
  • Control: ON/OFF, single and double action PID.
  • Measurement Range: According to probe used (see range table).
  • Display Resolution: According to probe used (1/0.1/0.01/0.001).
  • Overall Accuracy: +/- 0.5% fs.
  • Max Cold Junction Compensation Drift (in tc): 0.1 °C/°C with operating temperature 0 ... 50 °C after warm-up of 20 min.
  • Sampling Rate: 130 ms.
  • Display: 4-digit Red h 12 mm.
  • Compliance: ECC directive EMC 89/336 (EN 61326), ECC directive LV 73/23 and 93/68 (EN 61010-1).

Usage Features:

The ELK 38 features a user-friendly interface with a "P" key for accessing programming parameters and confirming selections, and "UP" and "DOWN" keys for adjusting values and navigating menus. A "U" key is programmable for various functions such as activating Auto-tuning/Self-tuning, swapping to manual control, silencing alarms, changing the active Set Point, or deactivating control.

Fast programming of the active Set Point and alarm thresholds is possible. Parameters can be made visible or hidden in the "OPEr" (Operating parameters) or "ConF" (Configuration parameters) menus, allowing customization of the user interface. The instrument supports up to four pre-programmed Set Points, selectable via parameter or the "U" key.

The display can visualize various process variables, control power, active Set Point, or alarm thresholds. A shift index function with three LEDs indicates whether the process value is within, below, or above a defined range relative to the Set Point.

Calibration of measurements is possible at two points using "OFSt" (Measuring Offset) and "rot" (Rotation of the measuring straight line) parameters, allowing the instrument to be recalibrated according to specific application needs. An input digital filter ("FiL") can be programmed to reduce noise sensitivity.

Maintenance Features:

The ELK 38 is designed for reliability and ease of maintenance. Error signaling provides clear indications of problems such as probe interruption, out-of-range measurements, or auto-tuning failures. The manual provides troubleshooting steps for these error conditions, including verifying probe connections, checking actuator functioning, and repeating auto-tuning processes.

For cleaning, a slightly wet cloth with water is recommended; abrasive cleaners or solvents should be avoided to prevent damage to the instrument. The instrument is covered by a 12-month warranty against manufacturing flaws or faulty material. Opening the housing, violating the instrument, or improper use/installation will void the warranty. In case of a faulty instrument, users are advised to contact the sales department for authorization before shipping the product for repair, along with a detailed description of the faults.

elco ELK 38 Specifications

General IconGeneral
Brandelco
ModelELK 38
CategoryController
LanguageEnglish