25-1000-UM 5
13. Relay outputs: 4 form C alarm relay output contacts
14. Operating Temperature: -4
o
F to 131
o
F (-20
o
C to 55
o
C)
15. Analog outputs: 4-20 mA, or optional 0–1.00 mA
16. Serial Communications: DNP 3 or optional Modbus serial (RS485) interface. Refer to serial communication
section, pages 11-14
17. Ground fault location: With optional handheld ground detector (25-1100-GF) "BB" option. Pulse
generator feature must be turned on, see setup menu table on page 7
18. High impedance measurement (option): For corrosion detection with current sensor p/n: 25-1100-H1
19. Annunciator port J1 (option): Used with p/n: 7-025-498-J3.0 External LED indication, ± ground fault, high
voltage, low voltage, excess ripple voltage and loss of AC to charger
20. DNP and Modbus serial communications protocols: See 826-501A.C DNP Profile document on
www.electroswitch.com/documents
Parameters and settings (as displayed in AUTO mode)
BAT Battery Voltage VDC
+BUS +BUS Voltage VDC
-BUS -BUS Voltage VDC
GFV Ground Fault Voltage VDC
RVV Ripple Voltage mV AC
RIV Ripple Current mA AC
TD Time Delay in Seconds
1PH/3PH Single/three Phase Power of AC charger
Alarms / Settings Description
Factory settings
(default)
Alarm setting
range
HI BAT High voltage alarm setting 142 VDC 125 to 150VDC
LO BAT Low voltage alarm setting 105 VDC 100 to 125VDC
+GND +GND fault alarm setting +13VDC 13 to 100VDC
-GND - GND fault alarm setting -13VDC -13 to -100VDC
RVV High ripple voltage alarm setting 0.200 V AC 0.005 to 2.000V AC
RIV Low ripple current alarm setting .010 A AC 0.005 to 2.000A AC
TD Time delay alarm limit setting
2 Sec 1 to 60 Sec
1PH/3PH
Phase selection, 1 Phase or 3 Phase
1 phase 1ph to 3ph
PON/POFF Pulse generator (Off/On) Pulse gen off Off/On
BON/BOFF Buzzer (Off/On) Buzzer off Off/On
LON/LOFF Latch relay (Off/On) (with all faults cleared Latch off Off/On
SYS Enable alarms and settings Factory defaults On/Off/Set
CAL Calibrate 4-20mA and voltage reading 4-20mA Adjust