EasyManua.ls Logo

Electroswitch 25-1000 - Page 8

Electroswitch 25-1000
17 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
25-1000-UM 8
15. CAL - Checking and/or Calibrating 4-20 or 0-1mA output and Voltage reading
Note: Use a certified digital multimeter which meets or exceeds the accuracy and resolution of your system
Timeout of CAL mode in 2 min if no buttons are pressed
1. Connect the DC current meters positive (+) lead to TB2-16 and the negative (-) lead to TB2-17,
2. ILO (low current limit) annunciator will be displayed, refer to operation flow diagram on page 10
3. Use the UP/DOWN button to adjust (if necessary) the low current limit to 4.00mA
4. Short-press the LIMIT button and go to the next calibration point, IHI (high current limit)
5. Use the UP/DOWN button to adjust (if necessary) the high current limit to 20.00mA
6. Connect the voltage input leads of your digital multimeter to TB1-1 and TB1-2
7. Short-press the LIMIT button and go to the next calibration point, VCAL
8. Use the UP/DOWN button to adjust (if necessary) the voltage readout to match the multimeter
ILO
Adjust 4.00 mA
or 0.0 mA
setting
IHI
Adjust 20.00 mA or 1.00 mA s
etting
VCAL
Adjust battery monitor voltage readout
9. Exit menu, press and hold LIMIT button for approx. 4 sec
16. ALARM LED Conditions
Flashing LED LED ON (Steady state)
Loss of AC power to charger High battery limit
Ripple voltage Limit Low battery limit
Ripple current limit +GND fault
High impedance limit -GND fault
17. Reset button
Press and hold resets alarms, relay contacts and annunciators
Note: All faults must be cleared in order to reset alarm relay contacts and annunciators
18. Limit button
Press and hold (4 sec) to navigate through setup or save settings and toggle through menu
19. T/R LED
Indicates transmitting and receiving indication, Red = Tx, Green = Rx
20. AUTO LED
Indicates unit is in AUTO Scanning mode