ELEKTROGAS – TECHNICAL MANUAL
4-13
Accessories and
optionals A fine mesh filter is provided, to prevent dirty contamination of the seal seat. However, an
external strainer must be installed upstream of the valve. Brass models are available without
internal filter only.
Inlet pressure chamber is provided with bilateral G1/4 gauges, to connect manometers,
pressure switches, leakage tester or other gas equipments. Flanged models are provided with
gauges in the outlet chamber too. Brass models are available without gauges only.
Models from DN65 to DN150 are provided with G1/8 connection on the bottom for closed
position indicator micro-switch (on request from 3/4" to 2"). To install the micro-switch the
installing kit must be required.
The threaded models Rp11/2 and Rp2 can be provided with flanged connections using an
optional kit.
Technical
specifications Tab. 1
Connections
Gas threaded ISO 7/1 from Rp1/4 to Rp2
Flanged PN16 – ISO 7005 from DN40 to DN150
Voltage rating
230 VAC 50/60 Hz
110 VAC 50/60 Hz
24 VAC/DC
12 VAC/DC
Voltage tolerance
-15% / +10%
Power consumption
see charts
Ambient temperature
-15°C / +60°C
Max. operating pressure
200 mbar (20 kPa)
360 mbar (36 kPa)
Flow capacity
see charts
Closing time
< 1 second
Opening time
< 1 second
Filter (except brass models)
600 µm, metal mesh
Protection class
IP54 (EN 60529)
Cable gland
ISO 16 (EN 50262) for terminal box
PG 9 for standard plug
Coil winding insulation
Class H (200°C)
Coil thermal resistance
Class F (155°C)
Materials in contact with gas
Aluminium alloy
Brass
Stainless steel
Plated steel
Anaerobic adhesive
Nitrile rubber (NBR)
Polytetrafluoroethylene (PTFE)