It is important to observe these instructions in order to guarantee safety for persons!
Do not discard these instructions!
Incorrect assembly can cause serious injury.
• Connections to the mains must be carried out by specialised personnel.
• The control must be disconnected from the mains during connestion work.
• The mains disconnection mechanism must be secured against unintentional and unauthorised
restarting and shoule always be accessible.
• Powered doors with pulsed or automatic operation must fulfil EN 12453.
• With external evaluation devices connect the 8.2 kOhm resistor in series with the switch contact.
• Caution: A moving door panel must not pose a risk of injury or damage.
• An 8.2 kOhm resistor can be connected in the CLOSED direction in the case of roller shutter drives.
• Caution: The roller shutters must not pose a risk of injury or damage.
180
130
60
230 V Mains terminals
Fuse
6,3 A tr.
Selector
switch
S 1
LED
S 2
Hold-open time
Proigramming
button
S 3
Integrated radio
receiver or slot for
radio receiver
24 V terminals
Operating appliances
Warning!
Advice: Only tubular drives with mechanical limit switches can be connected.