1
Technical Support Line +44 (0)2392 696638 G240xBM-x-y PAK200536_01G May 2016 Elmdene International Ltd ©
27.6V
DC
S
WITCH
M
ODE
P
OWER
S
UPPLIES
W
ITH
R
EMOTE
F
AULT
S
IGNALLING AND
B
ATTERY
M
ONITORING
Models:
G240xBM-y
Where ‘x’ is max load current and ‘y’ is Enclosure type
F
EATURES
High efficiency cost effective power supply ideal for use in Fire, Access Control and General Security applications.
Featuring a regulated 27.6Vdc output supplying continuous full rated current to load plus additional current for
charging 2 x 12V standby batteries. Maximum battery life is assured using deep discharge protection to prevent
premature battery failure when operating in standby mode for extended periods. Two sets of volt-free contacts are
provided to signal (i) loss of mains and (ii) battery and loss of output faults. The universal mains input voltage enables
the power supply to be used across a wide geographical area. The highly efficient switch mode design ensures low
operating costs, generates less heat and with a small physical size increases the room available for additional PCBs or
cables. The modular construction simplifies maintenance.
Continuous full rated current to load Reverse battery connection protection
Additional current to charge 2 x 12V standby
batteries
Modular construction for ease of maintenance and
installation
Battery Deep Discharge Protection
G2403 & G2405 - Full electronic short circuit and
overload protection on load output (under mains power
only)
Universal mains input voltage 90-264Vac G2401 & G2402 - Fuse protection
Volt free contact signalling mains failure Mains transient protection circuit
Volt free contact signalling output and battery faults Green Mains present LED
High efficiency electronics for reduced running costs
and lower operating temperatures
Yellow Fault LED
Installer safe design with all high voltage electronics
fully shrouded
Orange Battery Charging LED (visible on PCB only)
S
PECIFICATION
Input Specification
Voltage (rated) / (operating) 100-240Vac / 90-264Vac (Both at 50 – 60Hz)
Max Current / Input Fuse See Model Specification Table
Max standby Power 0.8W (No load and no battery connected)
Output Specification
Voltage
27.0 – 28.0Vdc (27.6Vdc nominal) on mains power
21.0 – 24.7Vdc on battery standby
Max load current / load fuse See Model Specification Table
Ripple 100 mV pk-pk max
Overload Electronic shutdown until overload or short circuit removed
(under mains power only) (G2403BM & G2405BM)
Fuse Protection (G2401BM & G2402BM)
Elmdene International Ltd
Tel: +44 (0)23 9269 6638
3 Keel Close, Interchange Park, Fax: +44 (0)23 9266 0483
Portsmouth,
Hampshire
,
PO3 5QD
, UK
www.elmdene.co.uk
Question and Answer IconNeed help?

Do you have a question about the Elmdene G240 BM Series and is the answer not in the manual?

Elmdene G240 BM Series Specifications

General IconGeneral
Mains Input Voltage230V AC
Output Voltage24Vdc
Battery TypeSealed Lead Acid
Operating Temperature-10°C to +40°C
EfficiencyUp to 85%
Weight2.5kg
ProtectionOverload, Short Circuit

Summary

27.6VDC SWITCH MODE POWER SUPPLIES

FEATURES

High efficiency, cost-effective power supply for Fire, Access Control, and General Security applications.

SPECIFICATION

Details input and output voltage, current, fuse, ripple, and overload specifications.

Standby Battery

Mechanical

Enclosure dimensions, max battery capacity, and weight for different models.

Environmental

Operating and storage temperature ranges for the PSU.

INSTALLATION INSTRUCTIONS

SIGNALLING OUTPUTS

Volt-free contacts for general faults and mains failure indication.

CONNECTIONS

Details for connecting power and standby battery, and fault outputs.

INSTALLATION INSTRUCTIONS

Load Output

Instructions for attaching load cable, applying mains power, and verifying operation.

Signalling Outputs

Connecting EPS and GEN fault outputs to control equipment.

Standby Battery

Procedure for connecting and testing standby batteries.

OPERATING INSTRUCTIONS

MAINTENANCE

LOCAL INDICATORS

Describes the status of Mains, Fault, and Charge LEDs.

COMPLIANCE

Lists European Directives met by the power supply unit.

DISPOSAL OF PRODUCT AT END OF LIFE

Guidelines for proper disposal of the product and batteries.