Page #4 background imageLoading...
Page #4 background image
page 4 of 9 008TA14 BU-094-A Revision : 7 Page 4 / 9
Autoscrolling
Menu values scroll through the menu by keeping the ‚▲ / ▼'-keys depressed .
Error Messages
When an error condition occurs, the display will indicate the error code after an approx. 20 second delay.
Error Code Messages
E01 RTD/Pt100 temp sensor short circuit or temperature below -76°F (-60°C)
E02 RTD/Pt100 temp sensor interrupt (open) or temperature above 770°F (410°C)
E03 Temp. sensor third wire missing/not connected or Resistance (R) is equal to or above 10 ohms
C00 passcode entry required
E07 Alarm/Fault relay K1 open
E08 Alarm/Fault relay K1 short circuit
E09 Internal error
Error codes E07...E09: controller fault condition.
Check device/controller type
After controller is energized, the controller model/type number appears (
C14 for model ELTC-14
), followed by
a 3 second delay after which the actual temperature will be displayed.
Switching Temperature Scales (degF to deg C / deg C to deg F)
Changing sensor probe type (P20) automatically changes the temperature scale and associated set
points to the respective temperature scale (e.g. sensor type 0 and 1 display in deg C / sensor type 2
and 3 display in deg F).

Other manuals for eltherm ELTC-14

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the eltherm ELTC-14 and is the answer not in the manual?

eltherm ELTC-14 Specifications

General IconGeneral
Brandeltherm
ModelELTC-14
CategoryTemperature Controller
LanguageEnglish

Related product manuals