page 6 of 9 008TA14 BU-094-A Revision : 7 Page 6 / 9
In this mode (when
P34 =
2) relay K2 switches independently from alarm delay timers (P32 and P33) when the
actual high/low temp threshold ranges are between high and low set points P30 and P31.
Alarm Relay Modes
(
P34
= 0 or 1): If, after initial power on, the actual temperature falls below the low temp alarm threshold (P31),
the alarm delay (P33) is used as the alarm relay to provide additional time for warm-up. In normal operating
conditions, the alarm delay P32 is used as an alarm delay parameter.
Controller Technical Data / Specifications
20A resistive/ max 250 VAC
8A resistive / max. 250 VAC
-13 to 131°F (-25 to.+55°C)
-22 to 140°F (-30 to.+60°C)
32 to 734°F (0 to 390°C), optional configuration
display range / resolution
-58 to 752°F (-50 to 400°C)
± 1K, ± 2 digits -58 to 752°F (-50 to 400°C)
display / relay indicators
Sensor: AWG 16…24 copper wire, length (exposed wire) 3/8” (9 to 10mm)
Others: AWG 14…24 copper single-wire, length (exposed wire) 1/4”
(5…6mm)