Chapter 1 Overview 3
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Table 1-1 Configuration of fixed- configuration system
Item NetSure 501 A41-S1
NetSure 501 A41-S2
NetSure 501 A91-S1
NetSure 701 A41-S1
NetSure 701 A41-S2
NetSure 701 A41-S3
NetSure 701 A41-S4
NetSure 701 A41-S5
Contorller
Model
M221S/M222S
Model
M820B
Model
M221S/M222S
Model
M221S/M222S
Model
M221S/M222S
Model
M221S/M222S
Model
M820B
Model
M221S/M222S
Rectifier
Model
R48-1800A/R48-2000/
R48-2000e
Standard
configuration
4 pieces
Model
R48-1800A/R48-2000/
R48-2000e
Standard
configuration
4 pieces
Model
R48-1800A/R48-2000
/R48-2000e
Standard
configuration
5
pieces
Model
R48-2900U/R48-300
0e/R48-3200/R48-35
00e/R48-4000e
Standard
configuration
3
pieces
Model
R48-2900U/
R48-3000e
R48- 3200
R48-3500e
R48-4000e
Standard
configuration
4
pieces
Model
R48-2900U/
R48-3000e
R48- 3200
R48-3500e
R48-4000e
Standard
configuration
4
pieces
Model
R48-2900U/
R48-3000e
R48- 3200
R48-3500e
R48-4000e
Standard
configuration
4
pieces
Model
R48-2900U/
R48-3000e
R48- 3200
R48-3500e
R48-4000e
Standard
configuration
4
AC power
distribution
L
N
PE/ 220Vac L
N
PE/220Vac 3P
N
PE/380Vac
3P
N
PE/380Vac
L
N
PE/380Vac 3P
N
PE/ 220Vac
3P
N
PE/ 380Vac
L
N
PE/ 220Vac
DC power
distribution
BLVD load route
2 × 16A/1P,
MCB
LLVD load route
2 × 63A/1P,
2 × 32A/1P
MCB
BLVD load route
2 × 10A/1P,
2 × 32A/1PMCB
LLVD load route
2 × 63A/1P,
2 × 32A/1P
MCB
BLVD load route
5 × 63A/1P,
5 × 32A/1P,
8 × 10A/1P
MCB
LLVD load route
Not configured
BLVD load route
1 × 10A/1P
MCB
LLVD load route
4 × 40A/1P
MCB
BLVD load route
4 × 63A/1P,
6 × 32A/1P,
2 × 10A/1P
MCB
LLVD load route
Not configured
BLVD load route
2 × 32A/1P,
2 × 16A/1P
MCB
LLVD load route
2
×
63A/1P,
4
×
32A/1P,
2
×
16A/1P MCB
BLVD load route
2 × 63A/1P
4 × 32A/1P,
4 × 10A/1P
MCB
LLVD load route
2
×
100A/1P
2
×
63A/1P,
2
×
32A/1P MCB
BLVD load route
2 × 32A/1P,
2 × 16A/1P
MCB
LLVD load route
2
×
63A/1P, 4
×
32A/1P MCB
Battery MCB 2 × 63A/1P 2 × 125A/1P 2 × 125A/1P 2 × 125A/1P 2 × 125A/1P 2 × 125A/1P 2 × 125A/1P 2 × 125A/1P
AC SPD 1 piece Optional Optional Optional Optional 1 piece
Optional 1 piece
DC SPD 1 piece Optional Optional Optional Optional 1 piece
Optional 1 piece
Max.size (mm) 483 × 360 × 222 483 × 360 × 222 483 × 360 × 400 483 × 360 × 267 483 × 360 × 267 483 × 360 × 267 483 × 360 × 400 483 × 360 × 267
BLVD contorller
mode
Contorller power-off Contorller power-on Contorller power-on Contorller power-on Contorller power-on Contorller power-off Contorller power-on Contorller power-off
Weight 25kg 25kg 25kg 25kg 25kg 25kg 25kg 25kg
Notes:
1. Temperature sensor and connected cables, remote monitoring unit, battery rack.
2. The way of outage for control is cutting off the battery, disconnecting the monitor and storage battery, monitor dropping out and communication broken up.