2.13.2 Defrost heater contactor coil (not supplied)
An On/Off output connection is provided on the electronic board for direct connection of a
customer-supplied contactor (coil) for convenience when the defrost option is included.
Terminals are male spade type. Coil voltage rating should be 220VAC and current ratings 30VA
(hold) and 330VA (inrush).
2.13.3 Evaporator fan contactor coil (not supplied)
An On/Off output connection is provided on the electronic board for direct connection of a
customer supplied contactor (coil) for convenience when the evaporator fan is included.
Terminals are male spade type. Coil voltage rating should be 220VAC and current ratings 30VA
(hold) and 330VA (inrush).
2.14 Dimensions in mm
The figures hereunder show the overall dimensions of the ZX condensing units:
Figure 3: Physical dimensions of ZXME020E, ZXME030E and ZXME040E (Single-fan units)