44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวัฒนา กทม. 10170. 
website: https://www.add-furnace.com/ โทร: 02-888-3472 
Line ID: @add11 e-mail: add028883472@gmail.com 
 
adjustable, is adjusted by loosening the locknut, if used, and 
turning the adjusting screw or handwheel clockwise to increase 
or counterclockwise to decrease the outlet pressure setting. 
Re-tighten the locknut to maintain the adjustment position. 
 
Shutdown 
First, close the nearest upstream block valve and then close 
the nearest downstream block valve (when used). Next, open 
the downstream vent valve. Since the regulator remains open 
in response to the decreasing downstream pressure, pressure 
between the closed block valves will be released through the open 
vent valve. 
 
Maintenance 
 
 
  !  WARNING   
 
To avoid personal injury or equipment damage, 
do not attempt any maintenance or disassembly 
without first isolating the regulator from system 
pressure and relieving all internal pressure. 
Regulators that have been disassembled for 
repair must be tested for proper operation 
before being returned to service. Only parts 
manufactured by Emerson Process Management 
Regulator Technologies, Inc. should be used for 
repairing Fisher
® 
regulators. Relight pilot lights 
according to normal startup procedures. 
Due to normal wear or damage that may occur 
from external sources, these regulators must 
be inspected and maintained periodically. The 
frequency of inspection and replacement of 
the regulators depends upon the severity of 
service conditions or the requirements of local, 
state, and federal regulations. Even under ideal 
conditions, these regulators should be replaced 
after 15 years from date of manufacture or sooner 
should inspection reveal the need. 
Failure to do the following could result in personal injury or 
property damage. Visually inspect the regulator each time a gas 
delivery is made for: 
1.  Improper installation; 
2.  Plugged or frozen vent; 
3.  Wrong regulator or no regulator in the system; 
4.  Internal or external corrosion; 
5.  Age of the regulator; 
6.  Any other condition that could cause the uncontrolled 
escape of gas. 
 
Make sure the regulator vent, vent assembly, or vent tube does 
not become plugged by mud, insects, ice, snow, paint, etc. The 
vent screen aids in keeping the vent from becoming plugged, 
and the screen should be clean and properly installed. 
Replace any regulators that have had water in their spring case 
or show evidence of external or internal corrosion. Checking for 
internal corrosion may require complete removal of the adjusting 
screw and shutdown of the gas system. Closely examine 
regulators directly connected to the container valve by means of 
a solid POL adaptor (horizontal mounting) for signs of corrosion. 
Correct any improper installations. 
Older regulators are more likely to catastrophically fail because 
of worn or corroded parts. Replace regulators over 15 years 
of age; other service or environmental conditions may dictate 
replacement of the regulator before it becomes 15 years old, 
refer to Fisher Bulletin LP-32. 
 
Regulator Repair 
Regulators that have been disassembled for repair must be 
tested for proper operation before being returned to service. 
Only parts manufactured by Emerson Process Management 
Regulator Technologies, Inc. should be used to repair Fisher 
regulators. Be sure to give the complete type number of the 
regulator when corresponding with the factory.