44 70 10170. 
website: https://www.add-furnace.com/  02-888-3472 
Line ID: @add11 e-mail: add028883472@gmail.com 
 
 
 
Table 1.  Outlet Pressure Ranges and Spring Selection 
 
O
u
T
l
ET PRESS
u
RE R
ang
E
(1)
, PSI
g
 (bar) 
3 to 15 
3 to 20 
5 to 35 
30 to 60 
35 to 100 
80 to 150
(2)
 
(0,21 to 1,03) 
(0,21 to 1,38) 
(0,34 to 2,41) 
(2,07 to 4,14) 
(2,41 to 6,90) 
(5,52 to 10,3)
(2)
 
1D892327022 
1D751527022 
1D665927022 
1D745527142 
1E543627142 
1P901327142 
Red 
Silver 
Blue 
Green 
Yellow 
Brown 
1.  All springs can be backed off to 0 psig (0 bar).  For the highest capacity and most accurate control, use the lowest-range spring that can be adjusted to the required setpoint. 
2.  �annot be used in anhydrous ammonia (NH
3
) applications. 
 
 
 
 
1.  Use qualified personnel when installing, operating, 
and maintaining these regulators. Before installation 
inspect for damage.  Make sure there is not any 
foreign material in the regulator and all tubing and 
piping are clean and unobstructed. 
2.  If installing the regulator at an outside location, 
point the spring case vent in the downward direction 
to protect it from getting plugged or from collecting 
moisture, corrosive chemicals, or other foreign 
materials.  Spring case vent orientation may be 
changed by rotating the spring case with respect to the 
regulator body. 
3.  Install the regulator so that flow is from the IN to 
OUT connection as marked on the regulator body. 
 
 
 
! 
WaRnIng
   
 
If using this regulator on hazardous 
gas or flammable fluid, make sure 
that the vented gas is piped to a safe, 
well-ventilated area.  Do not install a 
regulator so that the gas will be vented 
into a closed space.  This could result 
in a fire or explosion which could cause 
personal injury or equipment damage. 
 
4.  To remotely vent the spring case, remove the 
screen, if present, and connect 1/4-inch NPT piping 
or tubing to the spring case connection.  The piping or 
tubing should vent the spring case to a safe location, 
have as few bends as possible, and have a screened 
vent on its exhaust end that is weather resistant and 
always pointed in the downward direction. 
5.  Like most regulators, 64 Series regulators have 
outlet pressure ratings lower than inlet pressure 
ratings. Although types with internal relief include 
limited downstream overpressure protection, all 
types may require additional relief protection for 
some service conditions if the actual inlet pressure 
can exceed the regulator outlet pressure rating or 
the pressure ratings of any downstream equipment. 
Inspect a regulator periodically and after any 
overpressure condition. 
6.  Each regulator is factory-set for the pressure 
setting specified on the order. If no setting is specified, 
outlet pressure is factory-set at the midrange of the 
control spring. 
 
 
Startup 
Key numbers are referenced in Figure 2. 
1.  Slowly open the upstream and downstream 
shutoff valves while monitoring the outlet pressure 
with a gauge installed at some point downstream 
from the regulator. Pressure may also be monitored 
by installing a pressure gauge in the  unused 
outlet connection.