EasyManua.ls Logo

Emerson Liebert Remote Monitoring Panel - Agency and Certifications; Table 20 Electromagnetic Interference (EMI)-Emission Limits; Table 21 Electromagnetic Susceptibility (EMS)-Immunity Levels

Emerson Liebert Remote Monitoring Panel
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Specifications
23
4.1 Agency and Certifications
Safety Standard: IEC/EN/AS 62040-1-1 incorporating applicable portions of IEC/EN/UL/AS 60950-1
Certification: CE and UL 60950-1:2003, First Edition CSA C22.2 No. 60950-1-03 1st Ed.
Electromagnetic Compatibility Standard: IEC/EN/AS 62040-2 incorporating applicable portions
of emission and immunity standards as detailed in Tables 20 and 21 below.
Table 20 Electromagnetic interference (EMI)—emission limits
Standard IEC/EN/AS Class
Harmonic Current 61000-3-2 -
Voltage Fluctuations & Flicker 61000-3-3 -
Conducted RFI CISPR 22 A
Radiated RFI CISPR 22 A
Table 21 Electromagnetic susceptibility (EMS)—immunity levels
Standard
IEC/EN/AS Requirement Level Criterion
Electrostatic Discharge
61000-4-2
6 kV contact, 8 kV air 3 B
Radiated Electric Fields
61000-4-3
10 V/m 3 A
Fast Electrical Transients
61000-4-4
2 kV / 5 kHz (Power and Signal ports) 3 B
Surges
61000-4-5
Power port
2kV (common mode)
1kV (differential mode)
Signal port
1kV
3B
Continuous Conducted Interfer.
61000-4-6
10V 3 A
Magnetic Field at Power Freq
61000-4-8
30A/m - B
Voltage Dips and Short
Interruptions
61000-4-11
70%Ut:
1ms, 3ms, 10ms A
30ms, 100ms, 300ms, 1000ms B
40%Ut:
1ms, 3ms A
10ms, 30ms, 100ms, 300ms, 1000ms B
0%Ut
1ms A
3ms, 10ms, 30ms, 100ms, 300ms, 1000ms B
Low Frequency Signals
61000-2-2 10V 140Hz-250Hz-360Hz
—A

Table of Contents