MTEC.DXi.H/DXi.HF.GB-3 Use and Maintenance technical manual DXi.H/DXi.HF English
Emibyte DXi.H/DXi.HF Direct expansion close control
$FFHVVRULHVGHVFULSWLRQ
AA )ORRGLQJDODUP Water sensible probe, is already wired by Manufacturer. This option has to be installed under the unit by the
unit installation technicians.
AE (OHFWULFDOSRZHUVXSSO\GLIIHUHQWIURPVWDQGDUGManily, 230V three phase, 460V three phase, with 50/60Hz of frequency.
AL 6PRNHDODUPSmoke sensible probe installed inside of the unit which activate an alarm in case of smoke presence which stops
the fans and compressors.
B %DVHPHQWSuitable for installation on raised floors, it can be regulate from 170mm to 600mm. It is provided with adjustable
feets.
BAS
%DVHIUDPHIRUODWHUDOFRQQHFWLRQV
BC +RWZDWHUFRLOOne or two-row water coil, placed after the cooling coil to re-heating and/or the heating of treated air; provided
with modulating actuator and with three-way valve and controlled by the on board microprocessor. This option has the priority
when requested with the electric heaters (RE option).
BG
+RWJDVFRLOOne pr two-row water coil, placed after the cooling coil to re-heating of treated air; provided with three-way valve
(ON/OFF type) and controlled by the onboard microprocessor.
DH 'HKXPLGLILFDWLRQFRQWUROV\VWHPComposed by a humidity probe.
DP 'RXEOHSDQHOVInternal panels for closing the compartments affected by the air flow made with profiles in galvanized pre-
painted sheet steel, which allow the reduction of the noise transmitted through the paneling and a better air tightness even
without external panels; it allows the unit operation also during maintenance operations with the panels removed, such as filter
replacement.
(30
EPM7
$LUILOWHURSWLRQV)ODWHIILFHQF\ILOWHUVH30DQGH30VXSSOLHGDVDQRSWLRQDVDQDOWHUQDWLYHWRVWDQGDUGVRQHV
FR
6SDUHILOWHUVNLW&2$56(in alternative to to standard ones.
FRM6
6SDUHÀOWHUVNLWH30
FRM7
6SDUH¿OWHUVNLWH30
H
+XPLGLILHU: Immerse-electrode type for the modulating production of steam; it is made of a steam cylinder, a steam distributor, water
inlet and outlet valves and a maximum water level probe. The onboard microprocessor indicates when the steam cylinder needs to
be replaced in order to be able to make a maintenance during the unit operation.
IE
)XPLJDWHGZRRGHQFUDWHSDFNLQJAvailable on request for critical transports in order to assure a protection to the unit.
IH 563URWRFROVHULDOLQWHUIDFHAllows the communication between the unit and an external supervision system (the external
supervision system and the communication software are not provided with the unit; please contact the Manufacturer in order to
have more info about the available communication protocols).
IH-BAC
%$&1(73URWRFRO6HULDO,QWHUIDFHGateway to be connected to the microprocessor to allow the connection between the unit
and an external supervision system with BACNET protocol, for a remote control and monitoring of the unit. (Alternative to IH,
IH LON and IWG).
IH-LON
/213URWRFROVHULDOLQWHUIDFHGateway to be connected to the microprocessor to allow the connection between the unit and
an external supervision system with LON protocol, for a remote control and monitoring of the unit. (Alternative to IH, IH BAC
and IWG).
IM 6HDZRRGSDFNLQJFumigated seawood case and protection bag with hygroscopic salts, suitable for long sea transports.
IP 0DJQHWRWKHUPLFVZLWFKHVIRUDX[LOLDU\FLUFXLWVInstalled instead of fuses for auxiliary circuits protection.
IS1 &ODVVLQVXODWLRQPDWHULDOIn conformity to the main European regulations in force.
IWG
6103R7&3,33URWRFROVHULDOLQWHUIDFHElectronic card to be connected to the microprocessor to allow the connection
between the unit and an external supervision system with SNMP or TCP/IP protocol, for a remote control and monitoring of the
unit. (Alternative to IH, IH BAC and IH LON).
MF 3KDVHPRQLWRUElectronic device controlling the correct sequence and/or the eventual lack of one ot the three phases switching
off the unit if necessary.
MN
1HXWUDOZLUHODFNIRUSRZHUVXSSO\Unit general power supply without neutral wire; for IT power supplies the
Manufacturer has to release, after a check, the connection authorization.