Step 7(e): One empty breaker
and one Main CT
Common in European 1-phase homes
Uncommon in N. American homes
Secure the White (N)
, Red (L2), and Blue
(L3) wires from the wiring harness to the
neutral block (you can use a wire nut and
splicing wire if needed). Turn off an empty
MCB and secure the Black (L1) wire from
the harness to the hot lead from the MCB.
Need help?
emporiaenergy.com/support
support@emporiaenergy.com
1-844-EMPORIA (367-6742)
Any empty MCB size can be used
in this scenario (not limited to
15A)