What to do if the Monitor ADC fails on Enatel Motive Power FS9?
- CChristina BridgesSep 9, 2025
If there is a faulty MPC35 controller module, replace it ensuring the replacement is correctly configured.
What to do if the Monitor ADC fails on Enatel Motive Power FS9?
If there is a faulty MPC35 controller module, replace it ensuring the replacement is correctly configured.
How to fix module over temperature in Enatel Motive Power FS9?
If a charger module is overheating, check that the air inlet filter is not blocked and ensure the charger is installed without any obstructions to the air inlet and outlet.
What to do if there is a configuration error in Enatel Motive Power Battery Charger?
If the charger cannot provide the target output current, check that the controller configuration matches the quantity of power modules installed. Add charger modules if necessary. Also, ensure the BMID/battery requires less current than the modules or AC supply can support.
Why is there no output current from my Enatel Motive Power Battery Charger?
If the charger is failing to provide the required current, check that the operator has not been unplugging the battery mid-charge cycle, or that the charge profile has allowed the battery current to fall below 0.7A.
What does an Urgent Module Fail Alarm mean on my Enatel Motive Power FS9 Battery Charger?
If faulty charger modules are affecting the ability of the charger to charge the battery, replace the faulty charger module(s).
Why am I getting a Low Mains Alarm on my Enatel Motive Power FS9 Battery Charger?
A Low Mains Alarm indicates that the AC mains supply is low, or the charger modules may be overloaded. Check that the configuration of the charger suits the application.
How to resolve an Inlet Filter Alarm on Enatel Motive Power Battery Charger?
If the air inlet filter is blocked, clean the filter.
What does a Main Switch Alarm on my Enatel Motive Power Battery Charger mean?
If the front panel switch is in the STOP position, the charge will start when the switch is set to START.
Why is the finishing charge timing out on my Enatel Motive Power FS9 Battery Charger?
If the finishing charge part of the cycle is longer than expected, check that the charger configuration matches the battery. Regular timeouts may indicate a problem with the battery.
How to fix Module Fan Fail on Enatel Motive Power Battery Charger?
If there is a faulty charger module fan, replace the charger module.
Key safety guidelines for handling and operating the charger and batteries.
Step-by-step guide for connecting, starting, and completing a charging cycle with the charger.
Details non-urgent alarms like Inlet Filter, Low Mains, and Module Fan Fail, explaining their causes and implications.
Explains urgent alarms such as Main Switch, Module Over Temperature, and APC Voltage Imbalance.
Explains urgent battery alarms such as Over Discharged Battery, Reversed Battery, and Bulk Charge Timeout.
Lists common charger problems, their potential causes, and recommended remedies for resolution.
| Input Voltage | 90-264 VAC |
|---|---|
| Storage Temperature | -40°C to +85°C |
| Cooling Method | Fan cooled |
| Efficiency | 92% |
| Protection Features | Short Circuit, Over Temperature |
| Certifications | CE, UL |