The VSD-R 4-20mA Box is a specialized air compressor supervisory and control unit designed to integrate with Variable Frequency Inverter Drive (VFD) panels that feature a 4-20mA speed control input. It also functions in cooperation with a management system unit. This device allows a fixed-speed, load/unload air compressor to be converted into a variable speed unit with advanced management system supervisory and control functionality, providing total synergy with energy control and VSD compressor-aware functions of the management system unit. Each air compressor requiring VSD-R integration must be equipped with an individual VSD-R Box and VSD panel.
VSD-R 'mA' Box:
VSD/VFD Unit Basic Requirements:
Compressor Basic Requirements:
General Operation: The VSD-R Box controls the speed of an air compressor's main motor in response to pressure variations (demand). It can function as a standalone VSD air compressor unit or in conjunction with a management system. The VSD-R Box performs all pressure regulation functions and controls the compressor using load/unload commands, integrating with the compressor's pressure switch or remote load/unload input.
The main drive motor operates only when the compressor's controller requests it to run, ensuring all compressor controller proprietary and safety features remain intact. The VSD-R Box controls the compressor's main motor contactor(s), operating them in response to a run request from the compressor's controller. Power is applied to the VSD panel (5) and then to the main motor (6) only after the contactor(s) have energized correctly (4). The contactor(s) are used for safety isolation, energizing prior to power application and de-energizing after power removal, prolonging contactor service life.
Any star/delta timing or motor run-on time implemented in the compressor controller can remain. The VSD-R Box monitors the compressor's response to load requests, generating a fault if an incorrect response is detected. When loaded, the VSD-R Box varies the motor speed based on pressure demand. When unloaded but still running (run-on time), the motor runs at a predefined 'off load' speed. The main motor stops in a controlled manner when the compressor controller no longer requests it to run. In an emergency stop or trip, the VSD-R Box immediately removes power from the main motor and de-energizes the contactor(s).
User Interface and Display: The VSD-R features an LCD display showing the detected 'Delivery' pressure (primary display) and selected user menu items. Status symbols indicate system management unit activity, compressor running/loading status, service maintenance, and fault conditions. Indicators include a green LED for run status (off for not running, flashing for offload, on for loaded) and a red LED for fault status (off for no fault, flashing for fault).
Menu Navigation: The menu system allows access to various settings and information. Users can navigate through pages (P00, P01, P02, etc.) and items using UP/DOWN buttons. An access code is required for protected settings. The display can be locked on a selected menu item.
User Display Menu Items:
Operating Pressure Set Points (P01):
Error Log (P02): Stores the last 15 faults in chronological order, with '01' being the most recent.
Fault Codes: The VSD-R Box provides fault codes for various shutdown and alarm conditions:
Fault Reset: A fault code display can be reset by pressing the VSD-R Box RESET button once the fault condition is resolved.
Compressor Not Responding: If the compressor does not respond to a 'Remote Load' signal within 60 seconds, the VSD-R Box assumes the compressor is 'not available'. The 'remote load' signal is pulsed every 10 seconds until a response is detected, and the condition automatically resets. Users should check if the compressor has been started.
Compressor Faults: The VSD-R Box does not detect individual compressor faults; these should be viewed on the compressor controller. The VSD-R Box will detect any compressor shutdown or run inhibit as a 'not ready' signal, displaying a continuous 'Alarm' symbol and inhibiting VSD motor operation. The management system (if connected) will show the compressor as 'not available'.
Power Disruption Recovery: The VSD-R Box is always active and will automatically recover and become active when power is re-established after a disruption. It is recommended that the compressor controller has a 'power failure automatic restart' facility.
Pressure Regulation Control: If communications with the management system are disrupted, pressure regulation control defaults to 'local' (according to VSD-R Box upper and lower pressure settings). It automatically re-activates 'Remote regulation control' when communications are re-established.