EPF4T Series USER MANUAL
Power Factor Controller
The power factor controller was designed with signal processing
technology to ensure accurate control of all the electrical systems
of the plant such as: VOLTAGE, CURRENT, COS
φ
, THDI% and
through a sosticate algorithm, optimal use of capacitors bank
and contactors, taking into account the distortion phenomena of
industrial plants.
Using digital signal ltering techniques, it is able to separate
only the components from the other harmonic components
basic sinusoidal voltage and current, on which the phase shift is
measured.
The device consecutively displays all the measurements on the 4
digit 7 segment display in order to ensure easy reading of the data
in any environmental condition.
The user can access the adjustment using four user keys of the
instrument, manually insertion banks, displaying measurements
and alarms.
INSTALLATION
The power factor controller must be installed on a three-phase or
single-phase line with a 50-60 Hz mains frequency and quadrature
insertion. EPF need to be connected to a CT to measure the line
current (L1) and to the AC voltage (L2-L3) to measure the voltage
of the network.
The power supply inputs and the other connections of the device
must be protected by fuses suitably sized according to the regulations
in force and to the expected power consumption.
The control outputs must be suitably connected to the respective
intervention devices.
SET UP
EPF allows the setup of the parameters of the POWER FACTOR
and SENSITIVITY by pressing the NAV button until the LED
corresponding to the parameter to be changed lights up.
NOTE: The sensitivity is the time interval that the EPF regulator have
to wait between 2 consecutive insertions.
To access the SETUP menu it is necessary to set the device to
manual operation, switch off all the outputs and press the NAV
button for 3sec until the display shows PAR.
To select the parameter to modify press shortly the NAV button and
to change the value, press the buttons UP▲ o DOWN▼
The regolations to be made in this menu are:
A01 -> Current transformer ratio
A02 -> Power of each capacitor bank
A03 -> Capacitors nominal voltage
A04 -> RC time minimum time to wait between the disconnection of
a capacitor bank and a subsequent reconnection.
A05 -> Select three-phase or single-phase and 2 or 4 quadrant.
A06 -> Line Frequency (50-60Hz)
A07 -> High THDI% threshold
A08 -> Over THDI% threshold
A09 -> Over Temp threshold
NORMAL OPERATIONS
When the SETUP operations have been completed, the display
shows the value of the Power Factor currently calculated in the
plant, the voltage of line, current measured on the TA (true RMS) and
the Δ kVAr missing reactive power to reach the Set cosφ setpoint .
Note: if the measured power factor is not stable, reverse the
connections in terminals T1 and T2 of the input amperometric.
Press the NAV button to scroll through the various pages of the main
menu in the sequence:
Power Factor - Voltage - Current - Delta Power - SENS - SET cosφ-
THD I% - TEMP.
The segment of the NAV display shows the type of measure displayed.
Switching on the segment therefore indicates respectively whether
the display on the right corresponds to: Voltage, Current, Delta Power,
Sensitivity, THD I%, Set Power Factor, Temperature (the temperature
value is showed with the DOT led on).
Enerlux Power s.r.l.
Via G.Rossa, 6 - 46019 VIADANA (MN) Italy
Tel. + 39 0375 785887 - fax +39 0375 785877
info@enerlux.it
MAN_000008_eng_EPF_ed6_10_2019_enerlux
NAV
v
>
THD I
I
>
>
DELTA
>
>
>
SENS
TEMP
>
SET P.F.