P. PARAMETER DESCRIPTION UNI. L MİN. MAX. DEF P. PARAMETER DESCRIPTION UNI. L MİN. MAX. DEF
101 Off Mode Selection 2 0 1 0 2 Factory Password 3 0 9999 1923
102 High Voltage Alarm Level % 1 101 150 115 3 Service Password 2 0 9999 1922
103 Low Voltage Alarm Level % 1 50 99 85 4 User Password 1 0 9999 1934
104 High Frequency Alarm Level % 1 101 150 104 5 Parameter Record 1 0 2 0
105 Low Frequency Alarm Level % 1 50 99 96 6 LANGUAGE 1 0 1 0
110 Phase Sequence Control Action 1 0 1 1 7 Return to Factory Settings 3 0 1 0
111 Connection Type 2 0 1 1 8 Log Cleanup 3 0 1 0
301 Generator Connection Type 2 0 1 0 9 Engine Clock Setting 3 0 32000 0
302 Engine Type 3 0 1 0 10 Menu Timeout dk 3 1 30 5
303 Module Function 3 0 1 0 11 Exit Menu 1 0 1 0
304 Mode Function 1 0 3 0 201 Alternator Selection 2 0 1 1
305 Pre-Initialisation Action 2 0 2 0 202 Number of Alternator Poles 1 0 7 1
306 Starter Cut-off Level from Generator Frequency Hz 3 150 750 15.0 203 Nominal Voltage V 2 85 240 220
307 Starter Cut-off Level from Generator Speed rpm 3 500 6000 500 205 Generator High Voltage Alarm Action 3 0 4 4
308 Starter Cut-off Level from Generator Voltage V 3 60 500 173 206 Generator High Voltage Alarm Level % 2 101 150 115
309 Cranking Cut-off Level from Charge Alternator Voltage V 3 60 300 60 207 Generator Low Voltage Alarm Action 3 0 4 4
310 Starter Cut-off Level from Oil Pressure bar 3 10 100 3 208 Generator Low Voltage Alarm Level % 2 50 99 85
311 Maximum Number of Starter Attempts 2 1 10 3 209 Nominal Frequency Hz 2 300 600 50.0
312 Intermittent Horn Output 1 0 1 0 211 Generator High Frequency Alarm Action 3 0 4 4
313 Oil Pressure Unit bar 1 0 1 0 212 Generator High Frequency Alarm Level % 2 101 130 106
314 Low Oil Pressure Alarm Action 3 0 4 4 213 Generator Low Frequency Alarm Action 3 0 4 4
315 Low Oil Pressure Alarm Level bar 2 5 95 1 214 Generator Low Frequency Alarm Level % 2 50 99 94
316 Oil Pressure Switch Open Circuit Action 2 0 4 4 601 Initialisation Delay s 1 0 6000 50
317 Temperature Unit °C 1 0 1 0 603 Pre-run Time s 2 0 6000 20
318 High Coolant Temperature Alarm Action 3 0 4 4 604 Maximum Starting Time s 3 0 600 50
319 High Coolant Temperature Alarm Level °C 2 5 150 110 605 Starter Waiting Time s 3 50 990 100
320 Coolant Temperature Sender Open Circuit Action 2 0 4 4 606 Fault Control Delay s 3 0 1000 100
321 Low Fuel Level Alarm Action 3 0 4 4 607 Choke Duration s 1 0 600 20
322 Low Fuel Level Alarm Level % 2 0 45 5 608 Oil Pressure Switch Starter Cut-off Time s 3 0 50 0
323 Fuel Level Switch Open Circuit Action 2 0 4 4 612 Engine Warm-up Time s 3 0 3600 0
324 Fuel Pump Lower Limit % 2 0 90 20 613 Cooling Time s 3 0 18000 300
325 Fuel Pump Upper Limit % 2 5 95 80 616 Horn Duration s 2 10 900 30
326 Cooling Fan Low Limit °C 3 0 240 65 619 Low Oil Pressure Alarm Delay s 3 1 600 30
327 Cooling Fan High Limit °C 3 5 245 100 620 Oil Pressure Sender Open Circuit Delay s 2 1 600 30
328 Nominal Battery Voltage V 2 100 260 130 621 High Coolant Temperature Alarm Delay s 3 1 600 50
329 Battery High Voltage Alarm Action 3 0 4 4 622 Coolant Temperature Sender Open Circuit Delay s 2 1 600 50
330 Battery High Voltage Alarm Level % 2 101 125 125 623 Low Fuel Level Alarm Delay s 3 1 600 10
331 Battery Low Voltage Alarm Action 3 0 4 4 624 Fuel Level Sender Open Circuit Delay s 2 1 600 10
332 Battery Low Voltage Alarm Level % 2 75 99 75 631 Maintenance Alarm (Oil) Clock hr 3 200 10000 1000
334 Charging Alternator High Voltage Alarm Action 3 0 4 4 632 Maintenance Alarm (Air) Clock hr 3 200 10000 1000
335 Charging Alternator High Voltage Alarm Level % 2 101 125 125 633 Maintenance Alarm (Fuel) Clock hr 3 200 10000 1000
336 Charge Alternator Low Voltage Alarm Action 3 0 4 0 634 Maintenance Alarm (General) Clock hr 3 200 10000 1000
337 Charging Alternator Low Voltage Alarm Level % 2 75 99 75 635 Service Time Renewal 2 0 4 0
343 Maintenance Alarm (Oil) Action 2 0 4 2
344 Maintenance Alarm (Air) Action 2 0 4 2
345 Maintenance Alarm (Fuel) Action 2 0 4 2
346 Maintenance Alarm (General) Action 2 0 4 2
348 Number of Flywheel Teeth 2 0 1000 100
• NOTE: If the menu exit time has elapsed since the last entered password, the password screen is displayed. It is requested to enter the password
NOTE: Errors and alarms received while in the main menu are reset, but they are not removed from the main screen as information. When the
main screen is reached, reset button is pressed again.
NOTE: In test mode, when the start button is pressed for the first time, the genset is started, but if it is pressed for the second time, the genset
feeds the load.
NOTE: In the event of a fault or warning, the warning symbol is displayed in the lower right corner of the screen and the status bar flashes red
and blue depending on the level of the fault.