Installation Instructions
FOR USE IN AUSTRALIA
15MM THERMOSTATIC MIXING VALVE
Call 1300 369 273
www.enware.com
Enware Australia Pty Limited
9 Endeavour Rd Caringbah NSW 2229 Australia
Ph: +61 2 8556 4000 info@enware.com.au
AQUABLEND 1500
THERMOSTATIC
MIXING VALVE
WITH THERMAL FLUSH
I00103_Jul 18
NEW AQUABLEND 1500
FAQ and technical info available at
www.enware.com.au/1500info
I00105 VC463
IS123

Questions and Answers

  • B
    Brittany HernandezAug 3, 2025
    Why is the enware Aquablend 1500 mix temperature unstable?
    • K
      Karen HoodAug 3, 2025
      The mix temperature of your enware Control Unit might be unstable because debris is fouling the valve, the flow rate is below 4L/min, or the strainers are fouled. To resolve this, clean the valve to remove any debris, rectify any pressure deterioration, and clean the strainers.
  • A
    Anthony DawsonAug 12, 2025
    What to do if the enware Control Unit valve will not shut down?
    • L
      Lori GutierrezAug 12, 2025
      If the enware Control Unit valve won't shut down, it could be due to several reasons: the hot to mix temperature differential is not 10°C or greater, the piston O-ring is damaged, the valve body seat (Hot Seat) is damaged or fouled by debris, the cold seat (bottom surface of Top Cap) is damaged, the thermostatic element has failed, or the plastic shuttle of the thermostatic element has been damaged by debris. You can try the following: raise the hot water temperature, replace the piston O-ring, clean the seat using a mild descaling solution, replace the top cap, or replace the element.
  • C
    Casey ReedAug 21, 2025
    How to fix the enware Aquablend 1500 Control Unit if the desired mixed water temperature cannot be obtained?
    • P
      pmillerAug 22, 2025
      If you cannot obtain the desired mixed water temperature from your enware Control Unit, or the valve is difficult to set, the following reasons could be the cause: hot and cold supplies are fitted to the wrong connections, the valve contains debris, the strainers contain debris, non-return devices are damaged, or the top cap and/or piston O-rings are damaged. You can refit the valve with hot/cold supplies fitted to the correct connections, clean the valve ensuring that all debris is removed and components are not damaged, clean strainers ensuring debris is removed, check the non-return device is not jammed (clean if necessary), and check the top cap & piston O-rings for damage (replace if necessary).

Summary

Safety

Product Description

Recommended Pressures and Temperatures

Flow Sizing Graph

Installation

Commissioning of the Valve

Maintenance and Servicing

Cleaning the Strainers

Instructions for cleaning the valve's inlet strainers.

Non-Return Valve Operation

Procedure to check the functionality of the non-return valves.

Thermal Flush Option

Troubleshooting

Spare Parts

Commissioning Report

Servicing Report

Product Warranty

enware Aquablend 1500 Specifications

General IconGeneral
ModelAquablend 1500
Power SupplyNot applicable
Inlet Size15 mm
Outlet Size15 mm
Flow RateUp to 15 L/min