10
5.
Protection Unhealthy 1 N/C
6.7.2. CONTACT RATING
Carry continuously 5 A AC rms or DC
Make & Carry 20A for 0.2 sec
Break 50W DC with a max. of 300V or 5A DC
L/R 40msec
6.8. Burden
AC (1 Amps) 0.00006VA at 5mA
0.06VA at 250mA
AC (5 Amps) 0.00008VA at 25mA
0.2 VA at 1.25A
DC (Quiescent) 5W
7. ENVIRONMENTAL
7.1. Temperature IEC 60068-2-1/2
Operating Range - 10°C to + 55°C
Storage Range - 25°C to + 70°C
7.2. Humidity IEC 60068-2-3
4 days at 40°C and 93% RH
7.3. Transient Over voltage IEC 60255-5
5KV, 1.2/50µs, 0.5J between all terminals and Earth or between any two terminals
without damage or flashover.
7.4. Insulation IEC 60255-5
Variation
2.0KV rms for 1 min between all terminals and earth
2.0KV rms for 1 min between Independent circuits
1.0KV rms for 1 min across normally open contacts
7.5. High Frequency Disturbance IEC 60255–22–1, Class III
Variation
2.5KV Common (Longitudinal) Mode 3%
1.0KV series (Transverse) mode
3%