5.1 ENTER DATA IN SET MODE
SETUP / DISPLAY DESCRIPTION Range Code Default
00 LANGUAGE SEL.
SL ENGLISH
Display language selection SL
01 DIGITAL INPUTS
C0 DISABLE
ENABLE / DISABLE inputs from external contacts C0
02 OPERATION
C4b MANUAL
Operation Mode selection AUTOMATIC / MANUAL C4b
03 PULSE TIME
B2x 0.50 sec.
Pulse time from 0.05 to 5.00 sec. 0.05÷5.00 B2x 0.50 sec.
04 INTERVAL TIME
B3x 005 sec.
Interval time between ev. from 1 to 999 sec. 001÷999 B3x 5 sec.
05 POSTCL INT.
B3c 005 sec.
Interval time between ev. during post-cleaning from 1 to 999 sec. 001÷999 B3c 5 sec.
06 POST CYCLES
D1x 002 cycles
Number additional cycles after fan stop 00÷99 D1x 5
07 ELECTROVAL.N.
B1b 016 ev.
Selection Number of electrovalves B1b
08 EV TEST
B10 001 OFF
TEST Manual activation of
every single ev. from keyboard
B10
09 HOURS COUNTER
D14a 00000 Hours
Operation hours-counter 0÷65535 D14a
10 ZERO dP ADJ.
C8 0.00 kPa
dP zero readout regulation C8 0.00
11 FAN THRESHOLD
D1bx 0.10 kPa
dP threshold for cycle activation after fan stop 0.01÷0.99 D1bx 0.10
12 MIN dP ALARM
C7c1 OFF
Minimum dP alarm threshold 0.01÷9.99 C7c1 OFF
13 dP STOP CYCLE
C1a 1.00 kPa
1st dP threshold, STOP cleaning since dP low 0.01÷9.99 C1a 1.00
14 dP START CYCLE
C1d 2.00 kPa
2nd dP threshold, START cleaning since dP high 0.01÷9.99 C1b 2.00