© 2014 UTC Fire & Security Americas Corporation, Inc. 1 / 6 P/N 13083-EN • REV J • ISS 10APR14
ESL 700 Series Conventional Smoke and Heat
Detector Installation Sheet
Description
The ESL 700 Series smoke or smoke with rate-of-rise heat
detectors have field-replaceable optical chambers. The
detector uses an optical sensing chamber to detect smoke and
a fixed-temperature heat sensor to detect heat from fire. For a
list of model numbers, see Table 1. For a list of accessories,
see Table 2.
Table 1: Model numbers
Number
Description
Head (sold separately from base)
711U
Two-wire photoelectric smoke detector head
713
-5U Two-wire rate-of-rise and 57°C (135°F) fixed
temperature heat detector head
721U
Two-wire photoelectric smoke detector, with
remote test
input and remote alarm/trouble LED output
721UT
Two-wire photoelectric, with rate-of-rise heat detector
head with remote test, alarm/trouble LED output
731U
[1] Two-wire photoelectric smoke detector head with
auxiliary relay (NC/NO) output
741U
Four-wire
photoelectric smoke detector with alarm relay
(NO) output and remote alarm/trouble LED output
741UT
Four-wire photoelectric smoke and rate-of-rise heat
detector head, alarm relay (NO) output and remote
alarm/trouble LED output
731L
(OEM only, not for resale) see 731U description
Base (sold separately from head)
701U
Three-terminal base for 711U and 713-5U heads, 6 in.
(15 cm) base, connectors
Number
Description
702E
-
10PKG
Six-terminal base for all heads; 4 in. (10 cm)
702U
Six-terminal base for all heads, 6 in. (15 cm)
702RE
Six-terminal base for 731U, 4 in. (10 cm)
702RU
Six-terminal base for 731U, 6 in. (15 cm)
Head
with base (sold together)
TS7
-4 Four-wire photoelectric smoke detector
with alarm relay
(NO) output and remote alarm/trouble LED output
[1] UL Listed for releasing devices such as electromagnetic door
holders, fire dampers, or smoke dampers.
High voltage (120 V) base and head
The 702RE and 702RU bases have a special plastic protrusion
built in to prevent insertion of a low-voltage detector head into
a base containing damaging high voltages (120 V). These
bases can only be used with 731U heads. The 731U includes
auxiliary relay contacts and is only required when connecting
high voltage to the auxiliary relay.
Note: The 731U heads can also be used with 702E and 702U
bases for low voltage applications.
Table 2: Accessories
Number
Description
204
-12/24V End-of-line, power supervision relay for four-wire
applications
211
-10PKG Replaceable optical chamber for ESL smoke
detectors (set of 10)
706U1A
[1] Remote i
ndicator with red alarm LED, for use with
721U and 741UT
706U2A
[1][2] Remote indicator with red alarm LED and keyed
remote test, for use with 721U and 721UT
706U3A
[1][2] Remote indicator with red alarm LED, keyed
remote test and reset, for use with 721U and
741UT
SM
-200 Smoke! In A Can (canned smoke) for functional
testing of smoke detectors
SM
-EXT1 Extension tube for Smoke! In A Can
[1] The remote alarm/trouble LED
on the 706U1A, 706U2A, and
706U3A models work
s with both two-wire 721U/721UT and four-wire
741U/741UT models when connected as shown
in Figure 6 item
7 and
Figure
7 item 11.
[2] 706U2A and 706U3A only work with the 721U/721UT
two-wire
models, when connected as shown in Figure 6 item 6.
Question and Answer IconNeed help?

Do you have a question about the ESL 700 Series and is the answer not in the manual?

ESL 700 Series Specifications

General IconGeneral
Sensor TypePhotoelectric
Alarm Sound Level85 dB at 10 feet
Hush FeatureYes
Test ButtonYes
TypeSmoke Alarm
Power Source9V battery
LED IndicatorYes
ComplianceUL 217

Summary

Description

High voltage (120 V) base and head

Details regarding the use of 702RE and 702RU bases with 731U heads for high voltage applications.

Installation

Placement and spacing

Guidelines for optimizing detector placement and reducing false alarms for smoke and heat detectors.

Installing the base

Steps for selecting and installing the base unit onto an electrical box or ceiling.

Wiring

End-of-line supervision for four-wire systems

Requirement for supervision of power wiring in four-wire systems using a power supervision unit.

Testing

Testing the wiring for continuity

Procedure to check system wiring for continuity after base installation and end-of-line device.

Testing the smoke detector

Annual procedure for testing smoke detector functionality using Smoke! In A Can and sensitivity tests.

Testing the heat detector

Procedure to test the heat detector functionality using a hot air gun.

Maintenance

Cleaning the smoke detector

Steps for cleaning the smoke detector's optical chamber and replacing it with a new one.

Specifications

Regulatory information

Related product manuals