About this manual
■ Description of technical terms
The terms in this manual are defined as follows:
Servodrive is used to drive and control servo motor.
Servo System means a servo control system that includes the combination of a servodrive, servo motor with a host
computer and peripheral devices.
Parameters include monitoring parameter and setting parameters. Monitoring parameters can only be checked,
but not be modified, and setting parameters can be checked and modified, which includes function parameters and
data parameters.
■ Common symbol
The following symbols are used for convenience.
1. Instruction
P: position mode
Ptposition pulse mode
ALL: all modes
Printernal register position mode
S: speed mode
Srinternal register speed mode
Szanalog speed mode
T: torque mode
Trinternal register torque mode
Tzanalog torque mode
2. Usage of backslash (/)
Backslash is used in the wiring diagram. It describes the default logic of I/O interface.
For input signal (DI terminal), balckslash means, when input circuit is ON status, the input signal is valid, i.e. the
default logic is positive logic. Without blackslash means, when input side is OFF status, the input signal is valid,
i.e. the default logic is negative logic.
For output signal (DO terminal), backslash means output side circuit is common-opened, and when the signal is
output, the output side circuit is closed. Without backslash means output side circuit is common-closed, and when
the signal is output, the output side circuit is opened.
3. Others
NC: no connection
N/A: no unit

Table of Contents

Questions and Answers

  • H
    Heather DayAug 2, 2025
    What to do if EURA Servo Drives motor is in unlocked state?
    • D
      David ZavalaAug 2, 2025
      If the EURA Servo Drives motor is in an unlocked state, there are a couple of things to check: * First, examine if the servo drive enable signal is valid. See if the green light is on. If not, check if Po004=0; if it isn't, set it to 0 and power cycle the drive. Also, verify if Lo-15.A is 1; if not, ensure the wiring is correct. * Second, verify that the control mode is correct by checking Po001.X.
  • B
    ballardbonnieAug 18, 2025
    How to fix EURA Servo Drives when the digital tube or green light isn't lit?
    • D
      Destiny HartAug 18, 2025
      If the digital tube or green light on your EURA Servo Drives isn't lit, consider these potential causes: 1. The control terminal might be disconnected. Rewire and ensure the L1C/L2C power cable is connected to the socket separately. 2. There may be a control power supply fault. Check the voltage between L1C and L2C. Note that 380V servo drives do not need to connect to L1C and L2C. 3. There is a chance of a servo drive fault. In this case, please contact the manufacturer.

EURA SD20-G Series Specifications

General IconGeneral
CategoryServo Drives
SeriesSD20-G
Control ModePosition, Speed, Torque
Communication InterfaceRS-485, CANopen
Protection FeaturesOvercurrent, Overvoltage, Undervoltage