MAINTENANCE
.081/02-15 1-15
ITEM
DESCRIPTION INTERVAL
OIL FLUSHING
PROCEDURE FOR
EVOQUA
INTERMEDIATE
AND FINAL
HOUSINGS ONLY
Reduce loading on clarifier mechanism by lowering
sludge blanket as a minimum. It is preferred to drain
and clean tank. Stop and lock out drive motor. Drain
existing oil. Refill with a mixture of 50% Mobil Oil
Corp. Mobil System Cleaner and 50% of any gear
lube oil. Run unit for 4 hours. Stop and drain. Refill
with proper viscosity oil for anticipated weather.**
As
Required
For other gear reducers, see manufacturer's bulletins
in VENDOR INFORMATION section.
**Due to the viscosity of the oil, it can take several hours for a true reading to occur at
the sight gauge. Overfilling of oil will result in oil leaking into the collector.