h
Ceiling tile
thickness range
1-20mm
Ceiling tile
thickness range
1-20mm
SW
Mains supply
and Channel S1
Channel D1
Cable clamps can
be reversed to
reduce aperture
Channel D0
(QuickLink
connection)
Aspect ratio
(diameter : height)
Type
Max recommended
mounting height
Office
Mid Bay
High Bay
Switch
SW1
Switch
SW1
Digital Dimming
Luminaires Channel D1
D
D
L
N
E
DIGITAL BALLAST
Ch D0
Ch S1
Ch D1
Data & Control
Digital Dimming
IEC 60669-2-1
LS3043DR
SW L NLout
L
N
E
D
D
L
N
E
DIGITAL BALLAST
MORE
Switched Dimming
Luminaires Channel D1
+
–
L
N
E
ANALOGUE BALLAST
ANALOGUE BALLAST
L
N
E
+
–
L
N
E
MORE
Switch
SW1
Supply
Supply
Channel S1
Channel
S1
Channel D1 Channel D0
QuickLink Bus Internally Looped
To next
sensor
Low voltage LS3260
D D
Ch D0
DD
Ch D0
Loop in
Data & Control
Loop Out
DALI
DIMMING
LOAD
Supply
N
L
E
DIGITAL
DIMMING
LOAD
73mm
Ratchet Component x4
Ratchet
moulding
1
2
3
4
1
11 2 2
2
1 2
3
SWITCHING
LUMINAIRES
SWITCHING
LUMINAIRES
Removing the Terminal Cover
Remove spring
230VAC 15%
50-60Hz
+
_
Ch D0
Ch S1
Ch D1
Data & Control
Analogue Dimming
IEC 60669-2-1
LS3043AR
SW L NLout
230VAC 15%
50-60Hz
+
_
Ch D0
Ch S1
Ch D1
Data & Control
Digital Dimming
IEC 60669-2-1
IEC 60669-2-1
LS3043DR
SW L NLout
230VAC 15%
50-60Hz
+
_
Installation Instructions
LightSpot HD Dimming PIR Sensors
LS3000AR
● ● ●
LS3000D
● ●
LS3000DR
● ● ●
LS3243R
● ● ● ●
LS3043AR
● ● ● ● ●
LS3043DR
● ● ● ● ●
LS3000ARMB
● ● ●
LS3000DMB
● ●
LS3000DRMB
● ● ●
LS3000ARHB
● ● ●
LS3000DHB
● ●
LS3000DRHB
● ● ●
LS3243RMB
● ● ● ●
LS3043DRMB
● ● ● ● ●
LS3243RHB
● ● ● ●
LS3043DRHB
● ● ● ● ●
Part Number
Switching
Digital
Dimming
Analogue
Dimming
QuickLink
Office
Mid Bay
High Bay
Tilting Lens
Micro Detection -
High Sensitivity
Macro Detection -
Standard Sensitivity
3.5m
12m
16m
N/A
N/A
The sensor is more sensitive
to movement across the beam
compared with movement
towards the centre.
Only suitably qualified personnel should install this equipment
Add suffix F for flush mount or SM for surface mount
1.9:1
(27m diameter @14m height)
2:1
(20m diameter @10m height)
4:1
(10m diameter @2.5m height)
2.8:1
(7m diameter @ 2.5m height)
fig 1
fig 4fig 2 fig 3 fig 5
The sensor should be positioned on the ceiling in the centre of the occupied
space. This product is available in three different mounting height variants;
see fig.1 and the table below. Ensure that the maximum recommended
mounting height is not exceeded.
Avoid mounting next to an AC unit.
For additional information on
positioning please refer to Tilt
and Lock the Sensor, overleaf.
The following wiring diagrams show how to connect some of the more
fully-featured products listed in the product table above. For clarity, the wiring
for some of the lesser-featured products is not shown, but the wiring principles
are the same and equally applicable. Simply omit any sections that are not
relevant to the product being installed.
Two-Channel Application, One Channel Switching,
One Channel Digital Dimming (fig 3)
Single Channel Dimming Using Analogue
or Digital Ballasts (fig 4)
Analogue ballasts cannot be switched off from the control terminals, so it is
necessary to switch the mains power from the sensor as shown in the diagram
below. Although switching the mains power is not necessary with digital ballasts,
they may be wired this way in order to reduce the quiescent power consumption
in unoccupied areas to an absolute minimum.
Connecting Sensors together with QuickLink,
and Creation of an Additional Dimming Channel (fig 5)
The wiring diagram below shows how to connect sensors together using the
QuickLink Bus. QuickLink is a convenient way of wiring multiple sensors so
that they share information (e.g. occupancy) and are able to work in
harmony. Some sensors operate from a low voltage derived from the
QuickLink bus and therefore do not require a mains connection – this
enables fast and convenient installation. The Low Voltage Bus sensors
are not described in detail here (see QuickLink Bus Sensors Installation
Instructions for further information). It is permissible to connect up to four
sensors together in this way. No more than two mains-powered sensors
are allowed in a common connection.
NOTE:
1. Digital ballasts are normally
wired from an unswitched
supply.
2. The sensor will
automatically adjust to
control DSI or DALI
ballasts, but all ballasts
must be of the same type.
NOTE: To remove sensor
rotate Lockring and
pull up
50093557-001 / Dimming
Fixing to Ceiling – Standard Method
Installing the Sensor into Ceiling Tile
Electrical Connections
Fixing to Ceiling – Secure Lockring Method
(Available separately, please order lockring)
Positioning the Sensor
Macro
Detection
High Sensitivity Micro Detection
Macro
Detection