4 Battery installation / connection
4.1 Battery orientation
Install the battery in an upright position only. Never upside down or on the sides. Incorrect orientation may lead to
premature failure or pose a safety risk.
4.2 Battery Installation
Do not install the battery in a place where it is exposed to direct sunlight or sources of heat (e.g. engine
compartments, engine exhaust systems, electrical/hydraulic pumps or any other device which generates
heat under normal or exceptional operating conditions)
Keep any flammable material away from the battery and its connected loads or chargers
Do not install in compartments with zero clearance, always leave space around the battery for ventilation
and cooling
Li-ion batteries must always be kept in a well ventilated, dry, clean and dust-free environment
Never expose the battery to fire or extreme heat
Keep the battery dry and clean from dirt.
Battery surface should be cleaned with a soft, dry cloth made of non-electro conductive material
Under no circumstances should liquids, cleaning agents or solvents be used to clean a battery
4.3 Precautions for battery serial connection
Serial connection of the blocks is not permitted.
4.4 Precautions for battery parallel connection
Maximum number of batteries in parallel is listed in table 2.1.
The batteries connected in parallel should be of the same model, voltage and preferably from
the same batch.
Ensure that all cables for parallel connection are identical (length, section and insulation).
The load should be connected diagonally (same voltage drop for each block).
Before connecting batteries in parallel, all batteries must be fully charged.
5 Instructions for safe handling
5.1 Leaking Batteries
If a battery leaks electrolyte, avoid contact with the leaking liquid or gas. If exposed to the leaking substance,
immediately perform the actions described below:
Inhalation: Evacuate the contaminated area, and seek medical attention.
Contact with eyes: Rinse eyes with flowing water for 15 minutes, and seek medical attention.
Contact with skin: Wash the affected area thoroughly with soap and water, and seek medical attention.
Ingestion: Induce vomiting, and seek medical attention.
5.2 Fire
Use CO
2
, Dry Powder or Foam extinguisher if available.
Use copious amounts of water or sand to cover the battery if available.