EasyManua.ls Logo

F&F LE-03MW CT - Page 13

F&F LE-03MW CT
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LE-03MW CT user manual
13
Register
Feature Type R/W Quantity
Settings
Dec
Hex
0
0
Serial number
U32
R
2
1
2
Meter Modbus address
U16
R/W
1
1÷247
2
3
Baud rate
U16
R/W
1
1200, 2400, 4800,
9600
3
4
Software version
Float
R
2
6
6
Hardware version
Float
R
2
8
8
Current transformer CT
U16
R/W
1
List of setting codes in
the table below
9
9
Configuration of the pulse output
Float
R/W
2
12000, 1200, 120, 12
11
B
Parameter calculation option:
- Total active energy
- Total reactive energy
U16
R/W
1
1 total energy
= consumed energy,
5 total energy
= consumed energy,
+ energy exported
9 total energy
= consumed energy
- energy exported
13
D
View display time
U16
R/W
1
1÷30
14
E
L1 Phase voltage
Float
R
2
16
10
L2 Phase voltage
Float
R
2
18
12
L3 Phase voltage
Float
R
2
20
14
Frequency
Float
R
2
22
16
L1 Phase current
Float
R
2
24
18
L2 Phase current
Float
R
2
26
1 A
L3 Phase current
Float
R
2
28
1C
Total active power
Float
R
2
30
1E
L1 phase active power
Float
R
2
32
20
L2 phase active power
Float
R
2
34
22
L3 phase active power
Float
R
2
36
24
Total reactive power
Float
R
2
38
26
L1 phase reactive power
Float
R
2

Related product manuals