Fieldpiece MR45 - A2 L Refrigerant Safety; Caution Statements

Fieldpiece MR45
19 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
76
Intentionally Blank
Make power connection of the recovery machine and other equipment
outside of the Temporary Flammable Zone
Bond the recovery machine outlet port to the recovery tanks unpainted
fitting with a grounding strap to dissipate static electricity build up
during during recovery process
Ensure area around machine is free of debris that could enter the
machine and cause accidental sparking
Always remain in attendance and observant when the machine is
running
Do not mix flammable refrigerants with air
Use an evacuated DOT recovery tank
If system has a suspected leak, stop recovery at 0 psig/bar to prevent
air from entering the recovery tank
After recovery, purge system with 100% nitrogen before opening
system for repair
!
CAUTION
FAILURE TO HEED THESE HAZARDS AND ACTIONS CAN CAUSE
EQUIPMENT DAMAGE:
Ensure that recovery machine, hoses, tank and other equipment are in
good working condition
If the power cable is damaged, it must be replaced by the
manufacturer, its service agent, or similarly qualified persons in order
to avoid a hazard
Avoid overfilling recovery tanks by following refrigerant manufacturer’s
filling instructions and using a weight scale
Avoid cross contamination (mixing) of refrigerants
Ensure mesh screen filter is installed & clean (page 30)
Use a filter drier on the input port and change it often to protect
machine from contaminated refrigerants
Ensure power switch is OFF before plugging into power
Disconnect power and allow fan to stop before opening or servicing the
recovery machine
Perform a self test periodically (page 22)