EasyManua.ls Logo

Fike FAV - Page 21

Fike FAV
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Doc. 8.8503.00.9
Rev. April, 2018
PAGE / 19
The following procedure must only be performed by a Fike qualified Service Engineer, who has been assigned to
prepare and complete the de-commissioning of the above referenced Explosion Protection System.
Each step in the listed procedure must be adhered to and completion/acceptance of this form is mandatory. The
Service Engineer must check off each of the following steps. In the case of non-compliance, the observed discrepancy
must be corrected before completion of the system de-commissioning.
STEPS / DESCRIPTION
1. Use Fike system/project component location diagram to record and
verify the locations of all Fike system components for each zone and
system.
pass
fail
Remark/
Note No.
2. Control Panel to be Disarmed/Shutdown.
pass
fail
Remark/
Note No.
3. All Suppressor/Valve actuators to be shunted.
pass
fail
Remark/
Note No.
4. Power supply to the Control Panel to be Isolated by the Customer
and disconnected to prevent accidental reconnection. Fike to Verify.
pass
fail
Remark/
Note No.
5. Control Panel battery to be disconnected and removed for disposal.
pass
fail
Remark/
Note No.
6. Each actuator is to be removed and placed in a storage boss, to be
either stored on site or removed for disposal.
pass
fail
Remark/
Note No.
7. Verify that all Suppressor/valve gauges are reading zero, replace fill
valve cap loosely
pass
fail
Remark/
Note No.
ATTENTION: SYSTEM IS NOW DE-COMMISSIONED AND READY FOR
DISMOUNTING BY THE CUSTOMER/OWNER.